148 ACE-tronics G9 ASD Installation and Operation Manual
Deceleration Suspend Frequency
Program Fundamental Acc/Dec 1
When Enabled at F349, this parameter is used to set the frequency at which the
Deceleration Suspend function will activate.
During deceleration, this parameter sets the frequency at which deceleration
will stop and the motor will run at the setting of this parameter for the time
setting of
F353.
Direct Access Number F352
Parameter Type — Numerical
Factory Default 0.00
Changeable During RunYes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Deceleration Suspend Time
Program Fundamental Acc/Dec 1
When Enabled at F349, this parameter is used to set the duration of activation
of the Deceleration Suspend function when initiated by reaching the
Deceleration Suspend Frequency setting (
F352).
Once this parameter times out the deceleration rate will resume from the point
of suspension.
Direct Access Number F353
Parameter Type — Numerical
Factory Default 0.0
Changeable During RunYes
Minimum — 0.0
Maximum — 10.0
Units — Seconds
F352 F353