ACE-tronics G9 ASD Installation and Operation Manual 189
FM Voltage/Current Output Switching
Program Terminal Analog Output Terminals
This parameter is used to select the type of output signal provided at the FM
terminal (i.e., voltage or current).
The output voltage and current range is 0 – 10 VDC and 0 – 20 mA,
respectively.
See F005 for additional information on this setting.
Settings:
0 – 10 V
0 – 20 mA
Direct Access Number F681
Parameter Type — Selection List
Factory Default 0–10V
Changeable During RunNo
FM Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the FM output terminal. The
FM output terminal response may be set to respond inversely (-) or directly (+)
to the input signal.
See F005 for additional information on this setting.
Settings:
Minus (Negative Gradient)
Plus (Positive Gradient)
Direct Access Number F682
Parameter Type — Selection List
Factory Default Plus
Changeable During RunYes
FM Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the FM terminal.
Set the function of F005 to zero and then set this parameter to zero for proper
operation.
See F005 for additional information on this setting.
Direct Access Number F683
Parameter Type — Numerical
Factory Default 0.0
Changeable During RunYes
Minimum — -10.0
Maximum — +100.0
Units — %
AM Output Gradient Characteristic
Program Terminal Analog Output Terminals
This parameter sets the output response polarity of the AM output terminal.
The AM output terminal response may be set to respond inversely (-) or
directly (+) to the input signal.
See F670 for additional information on this setting.
Settings:
Minus (Negative Gradient)
Plus (Positive Gradient)
Direct Access Number F685
Parameter Type — Selection List
Factory Default Plus
Changeable During RunYes
AM Bias Adjustment
Program Terminal Analog Output Terminals
This parameter setting is used to ensure that a zero-level input signal produces a
zero-level output at the AM terminal.
Set the function set at F670 to zero and then set this parameter to zero for
proper operation.
See F670 for additional information on this setting.
Direct Access Number F686
Parameter Type — Numerical
Factory Default 0.0
Changeable During RunYes
Minimum — -10.0
Maximum — +100.0
Units — %
F681 F686