ACE-tronics G9 ASD Installation and Operation Manual 217
My Function Time Data 5
Program My Function My Function Data
This parameter is used to set the response delay of the My Function Time
Data 5 terminal.
The applied discrete input signal must be present at the input terminal of the
ASD for the time setting here for a system response.
Discrete terminal input activation that does not equal or exceed this setting will
be ignored.
Direct Access Number F932
Parameter Type — Numerical
Factory Default — 0.01
Changeable During RunYes
Minimum — 0.01
Maximum — 600.00
Units — Seconds
My Function Count Data 1
Program My Function My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output COUNT1 (ON Timer).
COUNT1 (ON Timer) outputs a 1 upon reaching the threshold setting of this
parameter.
Direct Access Number F933
Parameter Type — Numerical
Factory Default — 0
Changeable During RunYes
Minimum — 0
Maximum — 9999
Units — Pulses
My Function Count Data 2
Program My Function My Function Data
This parameter is used to set the pulse-count threshold value used to trigger the
discrete output COUNT2 (ON Timer).
COUNT2 (ON Timer) outputs a 1 upon reaching the threshold setting at this
parameter.
Direct Access Number F934
Parameter Type — Numerical
Factory Default — 0
Changeable During RunYes
Minimum — 0
Maximum — 9999
Units — Pulses
Input Function Target 1
Program My Function My Function Unit 4
This parameter plays a role in the setup of the My Function feature by
selecting the functionality of the programmable Input Function Target 1
terminal.
This setting assigns the function of the programmable Input Function Target 1
terminal to any one of the user-selectable functions listed in
Table 9 on pg. 241,
Table 10 on pg. 242, or Table 12 on pg. 245.
See F977 for additional information on this parameter.
Direct Access Number F935
Parameter Type — Selection List
Factory Default 0 (Disabled)
Changeable During RunYes
Input Function Command 1
Program My Function My Function Unit 4
This parameter is used to assign a user-selected logical operator to two user-
selected Input Function Target variables, enable a counter/timer function, or
perform a hold/Reset function.
Table 13 on pg. 247 lists the available selections. Their use and selection
requirements are described in an example at F977.
Direct Access Number F936
Parameter Type — Selection List
Factory Default — 0 (NOP)
F932 F936