H7 ASD Operation Manual 139
Accel/Decel Pattern #2
Program
Special Control Parameters
1 – #4 Settings
This parameter enables a user-selected preprogrammed output profile that
controls the acceleration and deceleration pattern for the #2 Accel/Decel
parameter.
Settings:
Linear
S-Pattern 1
S-Pattern 2
Direct Access Number F503
Parameter Type Selection List
Factory Default Linear
Changeable During Run — Ye s
Acc/Dec Group
No path available (Direct Access Only)
While operating using the LED Keypad Option this parameter selects the
accel/decel profile to be used during a multiple-accel/decel profile
configuration. The accel/decel setting for selections 1 – 4 may be found at
F009, F500, F510, and F514, respectively.
Note: If using the LCD EOI, press ESC from the Frequency Command screen
to access this parameter.
Direct Access Number F504
Parameter Type Selection List
Factory Default 1
Changeable During Run — Ye s
Acc/Dec Switching Frequency #1
Program
Special Control Parameters
Accel/Decel Special
This parameter sets the frequency at which the acceleration control is switched
from the Accel #1 profile to the Accel #2 profile during a multiple-acceleration
profile configuration.
Direct Access Number F505
Parameter Type Numerical
Factory Default 0.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
S-Pattern Lower Limit Adjustment
Program
Special Control Parameters
Accel/Decel Special
Sets the lower limit of S-pattern 1 and 2.
Direct Access Number F506
Parameter Type Numerical
Factory Default 25.00
Changeable During Run — Ye s
Minimum — 0.00
Maximum — 50.00
Units — %
F503 F506