64 H7 ASD Operation Manual
S5 Input Terminal Assignment
Program
Terminal Selection Parameters
Input Terminal
Assignment
S5
This parameter selects the functionality of the S5 input terminal.
Note: The S5 input terminal may be used without the ASD-Multicom option
board.
Without the ASD-Multicom option board the S5 terminal assignment
information will be stored in volatile memory. The terminal assignment
information will be lost if the system is powered down or reset.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable S5 terminal to 1 of the 68 possible
functions that are listed in Table 6 on pg. 67.
Direct Access Number F119
Parameter TypeSelection List
Factory DefaultUnassigned
Changeable During Run — No
S6 Input Terminal Assignment
Program
Terminal Selection Parameters
Input Terminal
Assignment
S6
This parameter selects the functionality of the S6 input terminal.
Note: The S6 input terminal may be used without the ASD-Multicom option
board.
Without the ASD-Multicom option board the S6 terminal assignment
information will be stored in volatile memory. The terminal assignment
information will be lost if the system is powered down or reset.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable S6 terminal to 1 of the 68 possible
functions that are listed in Table 6 on pg. 67.
Direct Access Number F120
Parameter TypeSelection List
Factory DefaultUnassigned
Changeable During Run — No
S7 Input Terminal Assignment
Program
Terminal Selection Parameters
Input Terminal
Assignment
S7
This parameter selects the functionality of the S7 input terminal.
Note: The S7 input terminal may be used without the ASD-Multicom option
board.
Without the ASD-Multicom option board the S7 terminal assignment
information will be stored in volatile memory. The terminal assignment
information will be lost if the system is powered down or reset.
In addition, the input terminal must be specified as Normally Open or
Normally Closed.
This parameter sets the programmable S7 terminal to 1 of the 68 possible
functions that are listed in Table 6 on pg. 67.
Direct Access Number F121
Parameter TypeSelection List
Factory DefaultUnassigned
Changeable During Run — No