82 H7 ASD Operation Manual
Custom V/f Five-Point Setting #4 Frequency
Program
Special Control Parameters
V/f Five-Point Setting
The Custom V/f Five Point Setting #4 Frequency sets the frequency to be
associated with parameter F197 (Custom V/f Five Point Setting #4 Voltage).
See F190 for additional information on custom V/f curves.
Direct Access Number F196
Parameter Type Numerical
Factory Default 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 400
Units — Hz
Custom V/f Five-Point Setting #4 Voltage
Program
Special Control Parameters
V/f Five-Point Setting
The Custom V/f Five-Point Setting #4 Voltage establishes the percentage of
the output voltage that is to be associated with the frequency setting of F196
(Custom V/f Five Point Setting #4 Frequency).
See F190 for additional information on custom V/f curves.
Direct Access Number F197
Parameter Type Numerical
Factory Default 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
Custom V/f Five-Point Setting #5 Frequency
Program
Special Control Parameters
V/f Five-Point Setting
The Custom V/f Five Point Setting #5 Frequency sets the frequency to be
associated with parameter F199 (Custom V/f Five Point Setting #5 Voltage).
See F190 for additional information on custom V/f curves.
Direct Access Number F198
Parameter Type Numerical
Factory Default 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 400
Units — Hz
Custom V/f Five-Point Setting #5 Voltage
Program
Special Control Parameters
V/f Five-Point Setting
The Custom V/f Five-Point Setting #5 Voltage establishes the percentage of
the output voltage that is to be associated with the frequency setting of F198
(Custom V/f Five Point Setting #5 Frequency).
See F190 for additional information on custom V/f curves.
Direct Access Number F199
Parameter Type Numerical
Factory Default 0.0
Changeable During Run — No
Minimum — 0.0
Maximum — 100.0
Units — %
F196 F199