H7 ASD Operation Manual 91
RX Speed Reference Setpoint #1 (%)
Program
Frequency Setting Parameters
Speed Reference
Setpoints
RX
This parameter is used to set the direction, gain, and bias of the RX input
terminal when this terminal is used as the control input while operating in the
Speed Control or the Torque Control mode.
Perform the following setup to allow the system to receive control input at the
RX input terminal:
•Program
Fundamental Parameters
Standard Mode Selection
Command Mode
Use Control Terminal Strip.
•Program
Fundamental Parameters
Standard Mode Selection
Frequency Mode #1
Use RX.
Provide a Run command (F or R).
Gain and Bias Settings
When operating in the Speed Control mode, the settings that determine the
direction, gain, and bias of the RX terminal are:
RX Speed Reference Setpoint #1 (frequency) (F217),
•the RX input signal level that represents RX Speed Reference Setpoint #1
(frequency): F216,
RX Speed Reference Setpoint #2 (frequency) (F219), and
•the RX input signal level that represents RX Speed Reference Setpoint #2
(frequency): F218.
When operating in the Torque Control mode, the settings that determine the
direction, gain, and bias of the RX terminal are:
RX Torque Reference Setpoint #1 (%) (F220),
•the RX input signal level that represents the RX Torque Reference
Setpoint #1 (%): F216,
RX Torque Reference Setpoint #2 (%) (F221), and
•the RX input signal level that represents the RX Torque Reference
Setpoint #2 (%): F218.
Once set, as the RX input voltage changes, the directional information, the
output frequency, or the output torque of the drive will vary in accordance with
the above settings.
This parameter sets the RX input level that represents RX Reference Setpoint
#1 (direction/torque/frequency). This value is entered as -100 to +100% of the
-10 to +10 VDC RX input signal range.
The input signal may be trimmed using F474 (Bias) and F475 (Gain).
Direct Access Number F216
Parameter TypeNumerical
Factory Default0.0
Changeable During Run — Yes
Minimum — -100.0
Maximum — 100.0
Units — %
Frequency Settings
Torque Settings
F216 F216