192 H9 ASD Installation and Operation Manual
AM Output Terminal Function
Program Termi na l Analog Output Terminals
This parameter is used to set the output function of the AM analog output
terminal. The AM analog output terminal produces an output current that is
proportional to the magnitude of the function assigned to this terminal. The
available assignments for this output terminal are listed in Table 6 on pg. 237.
Note: To read current at this terminal connect a 100 – 500 resistor from
the AM (+) terminal through the series Ammeter to the CC (-)
terminal.
AM Terminal Setup Parameters
F670 — Set AM Function
F671 — Calibrate AM Terminal
F685 — Output Response Polarity Selection
F686 — Set Zero Level
Direct Access Number — F670
Parameter Type — Selection List
Factory Default Output Current
Changeable During Run — Yes
AM Output Terminal Adjustment
Program Termi na l Analog Output Terminals
This parameter is used to calibrate the AM analog output.
To calibrate the AM analog output, connect an ammeter as described at
parameter F670.
With the drive is running at a known value (e.g., output frequency), adjust this
parameter until the associated function of parameter F670 produces the desired
DC level output at the AM output terminal.
See F670 for more information on this setting.
Direct Access Number — F671
Parameter Type — Numerical
Factory Default 512
Changeable During Run — Yes
Minimum — 1
Maximum — 1280
MON1 Terminal Meter Selection
Program Termi na l Analog Output Terminals
This parameter is used to set the output function of the MON1 analog output
terminal. The available assignments for this output terminal are listed in Table 6
on pg. 237.
The MON1 analog output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal.
Note: The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
more information on the function of this terminal.
MON1 Terminal Setup Parameters
F672 — MON1 Output Function
F673 — MON1 Terminal Meter Adjustment
F688 — MON1 Voltage/Current Output Switching
F689 — MON1 Output Gradient Characteristic
F690 — MON1 Bias Adjustment Set Zero Level
Direct Access Number — F672
Parameter Type — Selection List
Factory Default Output Voltage
Changeable During Run — Yes
M
F670 F672