H9 ASD Installation and Operation Manual 197
Display Unit Selection
Program Utilities Display Parameters
This parameter is used in conjunction with F702 to set the method in which the
frequency is displayed on the EOI.
The multiplier setting of F702 will be applied to the display of all frequencies if
all frequencies are selected at this parameter.
The multiplier setting of F702 will be applied to parameters F364, F365, F367,
and F368 ONLY
if PID Process Data is selected at this parameter.
Settings:
0 — All Frequencies
1 — PID Process Data
Direct Access Number — F703
Parameter Type — Selection List
Factory Default All Frequencies
Changeable During Run — Yes
Display Gradient Characteristic
Program Utilities Display Parameters
The ASD-displayed response to output speed changes will be displayed as
directly proportional or inversely proportional as a function of this parameter
setting.
Selecting Negative Gradient displays an increased output speed as going more
negative.
Selecting Positive Gradient displays an increased output speed as going more
positive.
Settings:
0 — Minus (Negative Gradient)
1 — Plus (Positive Gradient)
Direct Access Number — F705
Parameter Type — Selection List
Factory Default Plus
Changeable During Run — Yes
Display Bias
Program Utilities Display Parameters
In conjunction with the setting of F702, this parameter sets the bias of the EOI
speed display.
The frequency entered here will be multiplied by the setting of F702 and then
displayed as the zero value on the EOI.
Direct Access Number — F706
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
Change Step Selection 1
Program Utilities Display Parameters
In conjunction with the parameter setting of F708, this parameter sets the
amount that the output speed will increase or decrease for each speed command
change entered from the EOI using the Rotary Encoder.
Direct Access Number — F707
Parameter Type — Numerical
Factory Default 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (F011)
Units — Hz
F703 F707