92 H9 ASD Installation and Operation Manual
Input Terminal 15 (LI7) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the LI7 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable LI7 terminal to one of
the user-selectable functions listed in Table 5 on pg. 234.
Note: The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
more information on the function of this terminal.
Direct Access Number — F125
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Input Terminal 16 (LI8) Function
Program Terminal Input Terminals
This parameter is used to set the functionality of the LI8 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable LI8 terminal to one of
the user-selectable functions listed in Table 5 on pg. 234.
Note: The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 instruction manual (P/N 58686) for
more information on the function of this terminal.
Direct Access Number — F126
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Output Terminal 1 (OUT1) Function
Program Terminal Output Terminals
This parameter is used to set the functionality of the OUT1 discrete output
terminals O1A and O1B.
The O1A and O1B (OUT1) output terminals change states (open or close) as a
function of a user-selected event. See Table 8 on pg. 239 for listing the possible
assignments for the OUT1 terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Direct Access Number — F130
Parameter Type — Selection List
Factory Default — Low-Speed Signal
Changeable During Run — No
Output Terminal 2 (OUT2) Function
Program Terminal Output Terminals
This parameter is used to set the functionality of the OUT2 discrete output
terminals O2A and O2B.
The O2A and O2B (OUT2) output terminals change states (open or close) as a
function of a user-selected event. See Table 8 on pg. 239 for listing the possible
assignments for the OUT2 terminals.
In addition, the output terminals must be specified as Normally Open or
Normally Closed.
Direct Access Number — F131
Parameter Type — Selection List
Factory Default — RCH (Acc/Dec
Complete)
Changeable During Run — No
U
T1
U
T2
F125 F131