202 H9 ASD Installation and Operation Manual
Baud Rate (RS485 2-Wire)
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
establishing the Baud Rate of the communications link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — 9600
1 — 19200
2 — 38400
Direct Access Number — F800
Parameter Type — Selection List
Factory Default 19200
Changeable During Run — Yes
Units — bps
Parity (RS485 2- and 4-Wire)
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
establishing the Parity setting of the communications link.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Settings:
0 — No Parity
1 — Even Parity
2 — Odd Parity
Direct Access Number — F801
Parameter Type — Selection List
Factory Default Even Parity
Changeable During Run — Yes
ASD Number
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
assigning an identification (ID) number to each ASD in the communications
network.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F802
Parameter Type — Numerical
Factory Default 0
Changeable During Run — Yes
Minimum — 0
Maximum — 247
Communications Time-Out Time (RS485 2- and 4-wire)
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
setting the time that no activity may exist over the communications link before
the link is severed (Time Out).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Changes made to this parameter require that the power be cycled (off then on)
for the changes to take effect.
Direct Access Number — F803
Parameter Type — Numerical
Factory Default 0 (Off)
Changeable During Run — Yes
Minimum — 0 (Off)
Maximum — 100
Units — Seconds
F800 F803