H9 ASD Installation and Operation Manual 247
*OLI ASD Overload Load requirement in excess of
the capability of the ASD.
The carrier frequency is too high.
An excessive load.
Acceleration time is too short.
DC damping rate is set too high.
The motor is starting into a spinning load after a
momentary power failure.
The ASD is improperly matched to the application.
OLM Motor Overload Load requirement in excess of
the capability of the motor.
V/f parameter improperly set.
Motor is locked.
Continuous operation at low speed.
The load is in excess of what the motor can deliver.
*OLR Resistor Overload Excessive current at the
Dynamic Braking Resistor.
Deceleration time is too short.
DBR configuration improperly set.
*OP Over-Voltage DC bus voltage exceeds
specifications.
ASD attempting to start into a spinning motor after a
momentary power loss.
Incoming commercial power is above the specified
range.
Decel time is too short.
Voltage spikes at the 3-phase input; install inductive
filter.
DBR required.
DBR resistance value is too high.
DBR function is turned off.
Over-Voltage Stall feature is turned off.
System is regenerating.
Load instability.
Disable the Ridethrough function (F302).
OT Over-Torque Torque requirement is in excess
of the setting of F616 or F617
for a time longer than the setting
of F618.
ASD is not correctly matched to the application.
F616 or F617 setting is too low.
Obstructed load.
*POFF Control Under-Voltage Under-voltage condition at the 5,
15, or the 24 VDC supply.
Defective Control board.
Excessive load on power supply.
Low input voltage.
PtSt Reference Point Two speed-reference frequency
setpoint values are too close to
each other.
Two speed reference frequency setpoints are too close to
each other (increase the difference).
UC Under-Current With the Low-Current Trip
(F610) parameter enabled, the
output current of the ASD is
below the level defined at F611
and remains there for a time
longer than the setting of F612.
Output current too low.
* Reset ignored if active.
LED
Screen
LCD
Screen
Description Possible Causes