4.HYDRO UNIT
Engineering Data book
38
4
▼Outdoor unit HWS-1402H-E
Hydro unit HWS-1402XWH**-E
Rated cooling capacity and power input
* Rated cooling capacity and power input are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Cooling capacity and power input are measured in accordance with EN14511.
Rated condition 1
LWT=7°C
dT=5deg
Capacity kW 11.0
Power input kW 4.08
EER W/W 2.69
Rated water flow rate /min 31.5
Rated condition 2
LWT=18°C
dT=5deg
Capacity kW 11
Power input kW 2.65
EER W/W 4.15
Rated water flow rate /min 31.5
TO : Outdoor temperature (DB°C)
LWT : Leaving water temperature (°C)
dT : Delta temperature (deg)
Return water temperature - Leaving water temperature