4.HYDRO UNIT
Engineering Data book
39
Cooling capacity and power input
* Cooling capacity and power input are include are the data at rated compressor operating frequency
* Power input does not include water pump power.
* Cooling capacity and power input are measured in accordance with EN14511.
Capacity (kW)
LWT (°C)
7 10 13 15 18
TO
(°C)
20 13.95 15.48 16.82 17.53 18.34
27 12.60 13.98 15.19 15.83 16.56
30 12.01 13.33 14.49 15.10 15.80
35 11.00 12.21 13.27 13.83 14.47
40 8.83 9.80 10.65 11.10 11.62
43 6.81 7.56 8.21 8.56 8.95
Power input (kW)
LWT (°C)
7 10 13 15 18
TO
(°C)
20 3.14 3.21 3.26 3.27 3.30
27 3.57 3.64 3.70 3.72 3.76
30 3.77 3.85 3.91 3.92 3.97
35 4.08 4.17 4.23 4.25 4.29
40 3.84 3.85 3.85 3.87 3.88
43 3.25 3.23 3.23 3.22 3.22
EER
LWT (°C)
7 10 13 15 18
TO
(°C)
20 4.44 4.83 5.16 5.36 5.55
27 3.53 3.84 4.10 4.26 4.41
30 3.19 3.46 3.71 3.85 3.98
35 2.70 2.93 3.14 3.26 3.37
40 2.30 2.55 2.76 2.87 3.00
43 2.10 2.34 2.54 2.65 2.78
TO : Outdoor temperature (DB°C)
LWT : Leaving water temperature (°C)