Diagnostic functional operation
Defect
frequency
confirmation
Low pressure sensor error
When PS<0.07 MPa is detected for 90 sec or
more (cooling, defrosting).
When PS<0.07 MPa is detected for 10 minutes
or more (hot water supply, heating)
1. Check the connection (body or
connection wiring) of the low
pressure sensor.
2. Check the resistance value of
the low pressure sensor.
EEROM error
Inconsistency is detected once without verify
ACK after writing to EEPROM.
1. Replace the water heat
exchange control board.
Extended IC error
When the extended IC is abnormal.
1. Replace the water heat
exchange control board.
Communication error
Individual hydro units have a group line.
1. Replace the water heat
exchange control board.
Communication error
The capability of the hydro unit has not been
set.
1. Check the setting of the FC01
capability specifications.
HWS-803xx-E = 0012
HWS-1403xx-E = 0017
Setting error
When ZONE1 has not been set, while ZONE2
has been set.
1. Check the body DP-SW12_2,3.
Diagnostic functional operation
Defect
frequency
confirmation
TD sensor error Open or short circuit in the
discharge temperature sensor.
1. Check the resistance value
and connection of the discharge
sensor (TD).
TE sensor error Open or short circuit in the
heat exchange temperature sensor.
1. Check the resistance value
and connection of the heat
exchange temperature sensor
(TE).
TL sensor error Open or short circuit in the
heat exchange temperature sensor.
1. Check the resistance value
and connection of the heat
exchange temperature sensor
(TL).
TO sensor error
Open or short circuit in the outdoor
temperature sensor.
1. Check the resistance value
and connection of the outdoor
temperature sensor (TO).
TS sensor error
Open or short circuit in the suction
temperature sensor.
1. Check the resistance value
and connection of the suction
temperature sensor (TS).
TH sensor error
Open or short circuit in the heat-sink
temperature sensor.
1. Check the resistance value
and connection of the heat-sink
temperature sensor (TH).
TE, TS sensors error
Open or short circuit in the temperature
sensors.
1. Check for any wrong
installation of the heat exchange
temperature sensor (TE) and the
suction temperature sensor
(TS).