HX7+ ASD Quick Start Guide 97
Table 22. Specifications for Lugs/Cables for the 6-, 12-, and 18-Pulse Non-Sine Wave HX7+ ASD.
Model
Number
HX7+C4
Lug Size Range
Power
Module
Weight
(approx.)
6P&12P/
18P
Typical Cable
Size
AWG or MCM
3 Phase Input
3-Phase
Output
DBR
AWG
6-Pulse 12-Pulse 18-Pulse
AM, FM, II
Terminals
TB1
Ter mi na l
Strip
660
14 – 3/0 14 – 3/0
N/A
2 (4 – 500)
N/A
1
1000
#20
(3-Core
Shield)
#18
(2-Core
Shield)
830 1
11K
1/0 – 300
2 (14 – 1)
AND
(12 – 2/0)
1
13K
1/0 – 300
1
16K 1
20K
2 – 250
OR
1 – 600
Shipped with
bulk head
terminal.
1
1000/2550
26K
2 (1 – 250)
OR
1 – 600
2 (6 – 350) 1
1200/3425
39K
3 (3/0 – 500)
2 (3/0 – 250)
2 (4 – 500)
1 1200/3650
45K 1
1200/3900
51K40 1
Note: For Lug Size values, the non-parenthesized number indicates the quantity of cables to be used for the
parenthesized recommended size range [i.e., 2 - (1 – 250) = Two cables of sizes 1 to 250 MCM].
Shaded = 18-pulse option available.
Grounding Stud is 3/8–16 x 3/4 for above items.