HX7+ ASD Quick Start Guide 63
*OLI ASD Overload Load requirement in excess of 
the capability of the ASD.
• The carrier frequency is too high.
• An excessive load.
• Acceleration time is too short.
• DC damping rate is set too high.
• The motor is starting into a spinning load after a 
momentary power failure.
• The ASD is improperly matched to the application.
OLM Motor Overload Load requirement in excess of 
the capability of the motor.
• V/f parameter improperly set.
• Motor is locked.
• Continuous operation at low speed.
• The load is in excess of what the motor can deliver.
*OLR Resistor 
Overload
Excessive current at the 
Dynamic Braking Resistor.
• Deceleration time is too short.
• DBR configuration improperly set.
*OP Overvoltage DC bus voltage exceeds 
specifications.
• ASD attempting to start into a spinning motor after a 
momentary power loss.
• Incoming commercial power is above the specified 
range.
• Decel time is too short.
• Voltage spikes at the 3-phase input; install inductive 
filter.
• DBR required.
• DBR resistance value is too high.
• DBR function is turned off.
• Overvoltage Stall feature is turned off.
• System is regenerating.
• Load instability.
• Disable the Ridethrough function (F302).
OT Overtorque Torque requirement in excess of 
the setting of F616 or F617 for a 
time longer than the setting of 
F618.
• ASD is not correctly matched to the application.
• F616 or F617 setting is too low.
• Obstructed load.
*POFF Control 
Undervoltage
Undervoltage condition at the 5, 
15, or the 24 VDC supply.
• Defective Control board.
• Excessive load on power supply.
• Low input voltage.
PtSt Reference Point Two speed-reference frequency 
setpoint values are too close to 
each other.
• Two speed reference frequency setpoints are too close to 
each other (increase the difference).
UC Undercurrent Output current of the ASD is 
below the level defined at F611 
and remains there for the time 
set at F612.
* Reset ignored if active.
Keypad 
Display
Function Description Possible Causes