8-2-4. Heat operation
([MODE] button on the remote control is set the
Heat ( ) operation.)
Transferring of heat operation signal from indoor unit to
outdoor unit starts.
The indoor fan motor operates by the room tempera-
ture when selecting “AUTO” of “FAN” as shown in Fig.
8-2-6, and operates with a set air flow when selecting
“LOW ” to “HIGH ”.
However, to prevent cold draft, revolution speed of the
fan is restricted by indoor heat exchanger when air flow
is AUTO (Fig. 8-2-7) and starting of FAN Manual.
[Basic control]
*1,*2, *3 : Approximate revolution speed of M
+
and L to
linear accordingly to temperature.
Fig. 8-2-6 Setting of air flow
[Cold draft preventing control]
The upper limit of fan revolution speed is shown below.
Fig. 8-2-7 Cold draft preventing control
NOTES :
*1 : Stops for 2 minutes after thermostat-OFF.
*2 : 24°C when the set temperature is 24°C or more
Set temperature when the set temperature is
below 24°C
(Room temp
.
)
–
(Set temp
.
)
[FAN AUTO]
-0.5
-1
-1.5
-2.5
-2
*1
*2
*3
-5.0
-5.5
0
Set
temperature
M
+
HIGH
LOW
A+4
A–8
A+4
A–8
46
45
34
33
33
32
21
20
*2 *2
FAN
AUTO
Starting
of FAN
Manual
Approximate
revolution speed
of HIGH and SUL
linear by Tc.
HIGH
SUL
SUL (NOTE : *1)
Stop
8-2-3. DRY operation
([MODE] button on the remote control is set the
Dry ( ) operation.)
• Once the setting is made, the operation mode is
memorized in the microcomputer so that the same
operation can be effected thereafter simply by
pushing [START/STOP] button.
• Dry operation signal is transmitted to outdoor unit.
•
The Cooling operation giving priority to dehumidifying,
which restrains the indoor fan speed and compres-
sor motor speed, is performed.
•
The indoor fan motor operates as shown in Fig. 8-2-5.
(Fan speed is AUTO only.)
• The outdoor unit controls the outdoor fan relay R01,
R02 and R03, and the compressor motor speed
according to the operation command signal sent
from the indoor unit.
NOTE :
*1 : Middle motor speed between L– and SUL
SUL : Super ultra Low
Fig. 8-2-5 Setting of air flow
L-
*1
SUL
+2.5
+2.0
+1.5
+1.0
+0.5
-0.5
Set
temp.
0
(Room temp.) - (Set temp.)