8-3. Temporary Operation
Temporary Auto operation, existence of Auto Restart,
and Temporary Cooling operation can be set by the
TEMPORARY button of the indoor controller.
TEMPORARY button
OFF ON
After pushing button
for 3 seconds
After pushing button
for 10 seconds
8-3-2. Temporary cooling operation
When the TEMPORARY operation button keeps
pushed for 10 seconds, Cooling operation of which
compressor motor speed and the indoor fan speed
are fixed starts.
Compressor motor speed :
10 : 28 rps
Indoor fan speed : Low
When the TEMPORARY operation button is pushed
again, the operation stops.
Auto Restart function is unavailable.
8-3-1. Temporary auto operation
When the TEMPORARY button is pushed, the Auto
operation with set temperature fixed at 25°C starts.
Controlling is same as that of Auto operation by the
remote controller.
When the TEMPORARY button is pushed again, the
operation stops.
During Temporary Auto operation, operation by the
remote controller is accepted.
Using the Auto Restart function, the Temporary Auto
operation starts when power failure is reset.
TEMPORARY button
TEMPORARY button
Table 8-3-1
Control
Temporary Auto
operation start
Auto Restart
control select
Temporary Cooling
operation start