7. REFRIGERANT CYCLE DIAGRAM
7-1. Refrigerant Cycle Diagram
FILE NO. SVM-12051
NOTE :
The maximum pipe length of this air conditioner is 25 m. When the pipe length exceeds 15m, the additional
Max. : 25m
Deo
xidized copper pipe
NOTE :
Gas leak chec
k position
Refr
igerant flow (Cooling)
Refr
igerant flow (Heating)
INDOOR UNIT
T1
TO
Temp. measurement
Indoor heat
exchanger
Cross flo
w fan
Deo
xidized copper pipe
Outer dia.
: 6.35mm
Thickness : 0.8mm
Sectional shape
of heat insulator
Allowable height
difference : 10m
Allo
wable pipe length
P
Pressure measurement
Gauge attaching por
t
V
acuum pump connecting port
Muffler
Pulse
Modulating
v
alve at liquid side
Ø1.2 x 80
Ø
1.2 x 80
TD
4-way valve
Compressor
D
A111A1F-24F
TS
T2
Outdoor heat
exchanger
Split capilla
ry
Temp. measurement
Propeller
fan
Ref
rigerant amount : 1.05kg
OUTDOOR UNIT
Muffler
Muffler
TE
TC
TA
Min. : 2m
Chargeless : 15m
Charge
: 20g/m
(16 to 2
5m)
charging of refrigerant, 20g per 1m for the part of pipe exceeded 15m is required. (Max.
200g)
Strainer
Tcj
Outer dia. : 9.52mm
Thickness : 0.8mm
RAS-B10N3KVP-E / RAS-10N3AVP-E
RAS-B13N3KVP-E / RAS-13N3AVP-E