21
FILE NO. SVM-12051
7-2. O
p
eration Data
<Coolin
g
>
Tempeature
Model name Standard Heat exchanger Indoor Outdoor Compressor
condition(°C)
RAS- pressure
pipe temp. fan mode
fan mode revolution
Indoor
Outdoor
P (MPa)
T1 (°C) T2 (°C)
(rps)
27/19
35/- B10N3KVP-E 0.9 to 1.1 12 to 14 40 to 42 High High 37
B
13N3KVP-E 0.8 to 1.0 8 to 10 41 to 43 High High 59
B
16N3KVP-E
0.7 to 0.9
7 to 9
42 to 44
High
High
83
<Heating>
Tempeature
Model name Standard Heat exchanger Indoor Outdoor Compressor
condition(°C)
RAS- pressure
pipe temp. fan mode
fan mode revolution
Indoor
Outdoor
P (MPa)
T1 (°C) T2 (°C)
(rps)
20/-
7/6
B
10N3KVP-E
2.5 to 2.7
36 to 38
2 to 3
High
High
4
8
B
13N3KVP-E
2.7 to 2.9
40 to 42
2 to 3
High
High
65
B16N3KVP-E 2.9 to 3.1 49 to 51 1 to 2 High High 83
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m