– 44 –
Outdoor Unit : RAS-4M27YAV-E
<Heating>
NOTES :
Model of Indoor unit 10 : RAS-M10YKV-E, 13 : RAS-M13YKV-E, 16 : RAS-M16YKV-E
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bend.
(Thermistor thermometer)
(2) Connecting piping condition : 5 meters x 4 units (5m/each indoor unit)
Temperature
condition
Operating combination
(Unit)
Heat exchanger
pipe temp.
Indoor Outdoor
No. of
o
eratin
units
ABCD
Standard
ressure
P (MPa)
T1 (°C) T2 (°C)
Indoor
fan
Outdoor
fan
Com
ressor
revolution
(rps)
10 –––2.7 to 2.9 44 to 46 2 to 4 High MED 41
13 –––3.2 to 3.4 52 to 54 2 to 4 High MED 52
1 unit
16 –––3.6 to 3.9 53 to 55 2 to 4 High MED 56
10 10 ––2.7 to 2.9 45 to 47 0 to 2 High MED 62
13 10 ––2.8 to 3.0 45 to 47 0 to 2 High MED 64
16 10 ––2.9 to 3.1 46 to 48 0 to 2 High MED 66
13 13 ––2.9 to 3.1 46 to 48 0 to 2 High MED 67
16 13 ––3.0 to 3.2 47 to 49 –1 to 1 High MED 69
2 units
16 16 ––3.1 to 3.3 48 to 50 –1 to 1 High MED 71
10 10 10 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 72
13 10 10 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 72
16 10 10 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 72
13 13 10 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 73
16 13 10 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 73
13 13 13 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 73
16 16 10 – 2.3 to 2.5 38 to 40 –1 to 1 High MED 73
16 13 13 – 2.5 to 2.7 37 to 39 –2 to 0 High MED 74
16 16 13 – 2.5 to 2.7 37 to 39 –2 to 0 High MED 74
3 units
16 16 16 – 2.5 to 2.7 37 to 39 –2 to 0 High MED 74
10 10 10 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 72
13 10 10 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 72
16 10 10 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 73
13 13 10 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 73
16 13 10 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 73
13 13 13 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 73
16 13 13 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 74
20 / – 7 / 6
4 units
16 16 10 10 2.0 to 2.2 33 to 35 –2 to 0 High MED 74