33
Item
12. Indoor fan
ON output
Operation flow and applicable data, etc.
ON signal is output when the indoor fan is operating.
1. Control items
While the indoor fan is operating, DC12V is output between 1
and 6 of CN60.
2. Wiring
Description
A fan or etc can be used by
synchronized with the indoor unit.
3. Operation
While the indoor fan operating, the output is ON.
When thermo-off occurs during heating operation, the indoor
fan may perform ON/OFF operation. In this case, the output
keeps ON status.
The lead wire, which connects the indoor P.C. board and the
relay, should be long within 2m. If using a longer wire or if not
using a relay, a malfunction may occur.
The lead wire (length: 500mm) attached with connector, which
connects it to CN60 is prepared as article sold separately.
<Model: TCB-KBCN60OPE>
1
2
3
4
5
6
1
2
3
4
5
6
CN60
(6P)
Indoor
P.C. board
Relay
(Procured locally)
Within 2m
Red
Blue
Orange
Yellow
Brown
Black
1
2
3
4
5
6
500mm