– 35 –
Item
14. Auto restart
function
Operation flow and applicable data, etc.
Description
This product is designed so that, after a power failure, it can restart automatically in the same
operating mode as before the power failure.
INFORMATION
The product was shipped with Auto Restart function in the OFF position.
Turn it ON as required.
<How to set the Auto Restart>
• Remove the cover of the electric parts box by taking off the mounting screws (3 positions) and
pushing the hooking section. (The cover of the electric parts box remains hanged to the hinge.)
• There are the selector switches (SW02) on the P.C. board of the electric parts box.
No.3 of the selector switches (SW02) is provided for the selector switch. Select ON of No.3 of the
selector switches (SW02). (OFF: setting without Auto Restart, ON: setting with Auto Restart)
<Height list of ceiling possible to be installed>
Model
RAS-
M10SMUV-E, M10SMUCV-E,
M13SMUV-E, M13SMUCV-E
M16SMUV-E, M16SMUCV-E
Possible installed
ceiling height
Up to 2.7 m
Up to 3.5 m
Model
RAS-
Standard (Factory setting)
High ceiling (1)
High ceiling (2)
M10SMUV-E M13SMUV-E M16SMUV-E
M10SMUCV-E M13SMUCV-E M16SMUCV-E
2.5 to 2.7 m 2.5 to 2.7 m 2.5 to 2.9 m
——2.9 to 3.2 m
——3.2 to 3.5 m
SW02
No.1 No.2
OFF OFF
ON OFF
ON ON
<How to set the High ceiling switch>
• Remove the cover of the electric parts box by taking off the mounting screws (3 positions) and
pushing the hooking section. (The cover of the electric parts box remains hanged to the hinge.)
• There are the selector switches (SW02) on the P.C. board of the electric parts box.
No.1 and No.2 of the selector switches (SW02) are provided to select the height of the ceiling.
According to the ceiling height in the following table, select No.1 or No.2 of the selector switches
(SW02).
1
ON
ON
SW02
6H
2 3 4
1
ON
6H
2 3 4
FAN 1
FAN 2
RE-
START
RC A/B
A B
SW01
TS ADJUST
ON
OFF
1
ON
ON
SW02
6H
2 3 4
1
ON
6H
2 3 4
FAN 1
FAN 2
RE-
START
RC A/B
A B
SW01
TS ADJUST
ON
OFF
REMARKS
When using the high ceiling (1) or (2),
cold air may be felt due to the
temperature drop of discharge air.
15. High ceiling
select switch