4.2.2. Binary Output Object Instance
Binary output objects allow to control output terminals via BACnet
®
network.
Set the terminal function parameter(see below table) before control output terminals.
These commandable objects can be used for priority-array and relinquish-default
property.
Instance ID Object Name Description
Active /
Inactive
Access
Binary Output #0 RO 1 CMD FL terminal control. (f132 = 92) ON / OFF C
Binary Output #1 RO 2 CMD OUT1 terminal control. (f130 = 94) ON / OFF C
Binary Output #2 RO 3 CMD OUT2 terminal control. (f131 = 96) ON / OFF C
Binary Output #3 RO 4 CMD R2 terminal control. (f138 = 98) ON / OFF C
Binary Output #4 RO 5 CMD OUT3 terminal control. (f136 = 100) ON / OFF C
Binary Output #5 RO 6 CMD OUT4 terminal control. (f137 = 102) ON / OFF C
Binary Output #3,#4,#5 : These are enabled with ETB004Z(Expansion IO card option).
R=Read-only, W=Writable, C=Commandable.