E6581440
- 12 -
4.2.3. Binary Value Objects Instance
Binary value objects allow to monitor inverter status and send command such as
RUN/STOP command.
Commandable objects can be used for priority-array and relinquish-default property.
Binary
Value ID
Object Name Description
Active/
Inactive Text
Access
#0 RUN/STOP ACT
Indicates the drive run status
(This object access to parameter fd01 bit10)
RUNS/READY R
#1 FWD/REV ACT
Indicates the motor rotation’s direction
(This object access to parameter fd01 bit9)
REV/FWD R
#2 FAULT ACT Indicates the drive’s fault status FAULTED/NONE R
#4 HAND/AUTO ACT Indicates if the drive is locally controlled or not HAND/AUTO R
#6 MAINT REQ
Commutative operation time alarm status
(This object access to parameter fc91 bit10)
YES/NO R
#7 DRIVE READY
The VSD is ready and waits a start command
(This object access to parameter fd01 bit14)
READY/NOT
READY
R
#8 AT SETPOINT The VSD has reached the target speed REACHED/NO R
#10 RUN/STOP CMD Commands a drive start START/STOP C
#11 FWD/REV CMD Commands a motor direction’s change REV/FWD C
#14 FAULT RESET Command to reset faults RESET/NO C
#15 MBOX READ Command to read parameter READ/RESET W
#16 MBOX WRITE Command to write parameter WRITE/RESET W
#18 SP1PRESET Preset speed operation frequency 1 SP1/NONE C
#19 SP2PRESET Preset speed operation frequency 2 SP2/NONE C
#20 SP3PRESET Preset speed operation frequency 3 SP2/NONE C
#21 SPTSEL
Frequency priority selection
(This object access to parameter fa06 bit14)
ENABLED/OFF C
#22 CMDSEL
Command priority selection
(This object access to parameter fa06 bit15)
ENABLED/OFF C
R=Read-only, W=Writable, C=Commandable.