E6582051
- 43 -
6.5.9. f441 Power running torque limit level 1(Only for the VF-AS3)
f443 Regenerative torque limit level 1(Only for the VF-AS3)
Torque limit level is set up by 0.01% unit and the hexadecimal number.
For example: when “Torque limit level " is set up to “250%”, since the minimum unit is 0.01%,
250%=250÷0.01=25000=61A8H
6.5.10. f460 Speed control response 1(Only for the VF-AS3)
Speed control response is set up by 0.01% unit and the hexadecimal number.
For example: when “Speed control response " is set up to “1.0%”, since the minimum unit is 0.1%,
1%=1÷0.1=10=000AH
6.5.11. f461 Speed control stabilization coefficient 1(Only for the VF-AS3)
Speed control stabilization coefficient is set up by 0.01% unit and the hexadecimal number.
For example: when “Speed control stabilization coefficient " is set up to “1.00%”, since the minimum unit is
0.01%,
1%=1÷0.01=100=0064H