E6582051
- 46 -
6.5.14.
fd00
(Output frequency (real time))
The current output frequency is read into 0.01Hz of units and by the hexadecimal number.
For example, when the output frequency is 80Hz, 0x1F40 (hexadecimal number) are read.
Since the minimum unit is 0.01%,
0x1F40 (Hex.) = 8000(Dec.) * 0.01 = 80 (Hz)
Also about the following parameters, these are the same as this.
-
fd22
(Feedback value of PID (real time)) ............................. Unit: 0.01Hz
-
fd16
(Estimated speed (real time)) ....................................... Unit: 0.01Hz
-
fd29
(Input power (real time)) ............................................... Unit: 0.01kW
-
fd30
(Output power (real time)) ............................................ Unit: 0.01kW
6.5.15.
fd03
(Output current (real time))
The output current is read into 0.01% of units and by the hexadecimal number.
For example, when the output current of the rated current 4.8A drive is 50% (2.4A), 0x1388 (hexadecimal
number) is read out.
Since the minimum unit is 0.01%,
0x1388 (Hex.) = 5000 (Dec.) * 0.01 = 50 (%)
Also about the following parameters, these are the same as this.
-
fd05
(Output voltage (real time)) ............................................. Unit: 0.01% (V)
-
fd04
(Voltage at DC bus (real time)) ....................................... Unit: 0.01% (V)
-
fd18
(Torque) .......................................................................... Unit: 0.01% (Nm)*
* When the motor information connected to the drive set to the parameter (
f405
-
f415
), torque
monitor value "100%" is same as the rated torque of a motor in general.

Table of Contents

Other manuals for Toshiba TOSVERT VF-AS3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-AS3 and is the answer not in the manual?

Toshiba TOSVERT VF-AS3 Specifications

General IconGeneral
ModelTOSVERT VF-AS3
CategoryInverter
Overload Capacity150% for 60 seconds
Cooling MethodForced Air Cooling
Control MethodV/f control, Sensorless vector control
Braking UnitBuilt-in
Communication ProtocolsModbus RTU, DeviceNet, Profibus DP
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheat, Ground Fault
EnclosureIP20
Operating Temperature-10°C to +50°C
Humidity5-95% (non-condensing)
AltitudeUp to 1000m

Related product manuals