CONCRETE MOISTURE ENCOUNTER X5 USER GUIDE
23
Equilibration Time:
Allow at least 30 minutes for probe to reach
temperature equilibrium before measuring
relative humidity. It is vitally important that the
concrete is at the same temperature as the probe.
Even a slight difference in temperature will
produce a significant error in relative humidity
measurement. Check that meter readings do not
drift by more than 1% RH over a 5 minute period.
The sensor in the Hygro-i2 probe may take longer
to recover if exposed to readings above 93% and
can be damaged by prolonged exposure to high
humidity.