CVHE-SVX005B-EN
93
Leak Testing
WWAARRNNIINNGG
EExxpplloossiioonn HHaazzaarrdd!!
FFaaiilluurree ttoo ffoollllooww ssaaffee lleeaakk tteesstt pprroocceedduurreess bbeellooww
ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy oorr
eeqquuiippmmeenntt oorr pprrooppeerrttyy--oonnllyy--ddaammaaggee..
NNeevveerr uussee aann ooppeenn ffllaammee ttoo ddeetteecctt ggaass lleeaakkss.. UUssee aa
lleeaakk tteesstt ssoolluuttiioonn ffoorr lleeaakk tteessttiinngg..
WWAARRNNIINNGG
HHaazzaarrddoouuss PPrreessssuurreess!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn
aa vviioolleenntt eexxpplloossiioonn,, wwhhiicchh ccoouulldd rreessuulltt iinn ddeeaatthh oorr
sseerriioouuss iinnjjuurryy..
IIff aa hheeaatt ssoouurrccee iiss rreeqquuiirreedd ttoo rraaiissee tthhee ttaannkk
pprreessssuurree dduurriinngg rreemmoovvaall ooff rreeffrriiggeerraanntt ffrroomm
ccyylliinnddeerrss,, uussee oonnllyy wwaarrmm wwaatteerr oorr hheeaatt bbllaannkkeettss ttoo
rraaiissee tthhee ttaannkk tteemmppeerraattuurree.. DDoo nnoott eexxcceeeedd aa
tteemmppeerraattuurree ooff 115500°°FF.. DDoo nnoott uunnddeerr aannyy
cciirrccuummssttaanncceess aappppllyy ddiirreecctt ffllaammee ttoo aannyy ppoorrttiioonn ooff
tthhee ccyylliinnddeerr..
IImmppoorrttaanntt:: If leak testing is required, contact a Trane
Service Agency.
Recommended System
Maintenance
NNOOTTIICCEE
PPrrooppeerr WWaatteerr TTrreeaattmmeenntt RReeqquuiirreedd!!
TThhee uussee ooff uunnttrreeaatteedd oorr iimmpprrooppeerrllyy ttrreeaatteedd wwaatteerr
ccoouulldd rreessuulltt iinn ssccaalliinngg,, eerroossiioonn,, ccoorrrroossiioonn,, aallggaaee oorr
sslliimmee..
UUssee tthhee sseerrvviicceess ooff aa qquuaalliiffiieedd wwaatteerr ttrreeaattmmeenntt
ssppeecciiaalliisstt ttoo ddeetteerrmmiinnee wwhhaatt wwaatteerr ttrreeaattmmeenntt,, iiff
aannyy,, iiss rreeqquuiirreedd.. TTrraannee aassssuummeess nnoo rreessppoonnssiibbiilliittyy
ffoorr eeqquuiippmmeenntt ffaaiilluurreess wwhhiicchh rreessuulltt ffrroomm uunnttrreeaatteedd
oorr iimmpprrooppeerrllyy ttrreeaatteedd wwaatteerr,, oorr ssaalliinnee oorr bbrraacckkiisshh
wwaatteerr..
Condenser
Condenser tube fouling is indicated when the approach
temperature (the difference between the condensing
refrigerant temperature and the leaving condenser
water temperature) is higher than predicted.
If the annual condenser tube inspection indicates that
the tubes are fouled, two cleaning methods—
mechanical and chemical—can be used to rid the tubes
of contaminants. Use the mechanical cleaning method
to remove sludge and loose material from smooth-bore
tubes.
To clean other types of tubes including internally-
enhanced types, consult a qualified service
organization for recommendations.
Figure 61. Typical chemical cleaning setup
Pipe
Connections
Shutoff
Valves
Cleaning
Solution
Circulator
Pump
1. Follow all instructions in “Waterbox Removal and
Installation,” p. 95 to remove waterbox covers.
2. Work a round nylon or brass bristled brush
(attached to a rod) in and out of each of the
condenser water tubes to loosen the sludge.
3. Thoroughly flush the condenser water tubes with
clean water.
4. Scale deposits are best removed by chemical
means. Be sure to consult any qualified chemical
house in the area (one familiar with the local water
supply’s chemical mineral content) for a
recommended cleaning solution suitable for the
job.
NNoottee:: A standard condenser water circuit is
composed solely of copper, cast iron, and
steel.
NNOOTTIICCEE
UUnniitt CCoorrrroossiioonn DDaammaaggee!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn
ccoorrrroossiioonn ddaammaaggee ttoo tthhee uunniitt aanndd ttuubbeess..
FFoollllooww pprrooppeerr pprroocceedduurreess wwhheenn uussiinngg ccoorrrroossiivvee
cchheemmiiccaallss ttoo cclleeaann wwaatteerr ssiiddee ooff uunniitt.. IIff uunnssuurree,, iitt
iiss rreeccoommmmeennddeedd tthhaatt tthhee sseerrvviicceess ooff aa qquuaalliiffiieedd
cchheemmiiccaall cclleeaanniinngg ffiirrmm bbee uusseedd..
IImmppoorrttaanntt:: All of the materials used in the external
circulation system, the quantity of the
solution, the duration of the cleaning
period, and any required safety precautions
should be approved by the company
furnishing the materials or performing the
cleaning. Remember, however, that
whenever the chemical tube cleaning
method is used, it must be followed up
with mechanical tube cleaning, flushing,
and inspection.