28
SCXF-SVX01T-EN
Figure 14. Top view of self-contained unit showing
recommended service and code clearances(a)
Air Inlet
See Table
42” (1066.8mm) (20-38 Ton)
Minimum
48” (1219mm) (42-110 Ton)
Control
Panel
36” (914.4mm)
Minimum
Left side
Front
Right side
Note: (a) See for right side clearance values for various
unit configurations.
Table 14. Service and code clearance requirements
Side
Distance—inches (mm) Purpose
Front
42 (1066) (20 to 38 tons) NEC code requirements
48 (1219) (42 to 110 tons)
Fan service/removal
Left
36 (914) Filter, refrigeration, and waterside components
Right
9 (229) Non VFD w/open return
18 (457)
Non VFD w/ducted return
9 (229) 20 to 80 tons, w/VFD 7.5 to 50 hp
36 (914) 90 to 110 tons (motor, condensers, and refrigeration)
Inlet
18 (457) (20 to 80 tons)
Provides uniform airflow
36 (914) (90 to 110 tons)
Provides uniform airflow
Dimensional Data