SCXF-SVX01T-EN
39
Table 20. Fan motor electrical data (continued)
HP TYPE
200V 460V 575V
FLA LRA FLA LRA FLA LRA
50
ODP N/A N/A 59.0 378.0 47.0 305.0
TEFC N/A N/A 59.0 455.0 47.2 380.0
60 ODP N/A N/A 71.0 464.0 N/A N/A
Table 21. VFD electrical data
VFD L.I.C.
HP
Without Bypass With Bypass
200V 460V 575V 200V 460V 575V
7.5 23.8 10.6 8.8 32.2 10.6 8.8
10 32.2 14 11.1 48.3 14 16.6
15 48.3 21 16.6 61.9 21 16.6
20 61.9 27.6 21.4 78.2 27.6 21.4
25 78.2 34 26.3 92 34 26.3
30 92 41 31.2 117 41 31.2
40 117 53 39.9 139.2 53 39.9
50 NA 64 50.6 n/a 64 50.6
60 NA 77 NA n/a 77 n/a
Note: Values are at the maximum VFD input rating and not the reduced
motor values. L.I.C. = Line Input Current.
Table 22. Single stage electric heat electrical data
SXWF Size Heat Kw
200V Amps 460V Amps
20 18 50 21.7
22 18 50 21.7
25 18 50 21.7
29 23 63.8 27.7
32 23 63.8 27.7
35 27 75 32.5
38 27 75 32.5
42 31.5 87.4 37.9
46 31.5 87.4 37.9
52 39 108.3 46.9
58 39 108.3 46.9
65 48 133.2 57.7
72 48 133.2 57.7
80 48 133.2 57.7
Note: Electric heat amperage should not be considered when
determining minimum circuit ampacity. The current of the unit in
the heating mode will not exceed the current of the unit in the
cooling mode
Table 23. 2 stage electric heat electrical data
Unit Size
SCWF Heat kW
200V
Amps
460V
Amps
575V
Amps
90 76 N/A 95.39 N/A
100 76 N/A 95.39 N/A
110 76 N/A 95.39 N/A
Static Pressure Transducer
Installation (VAV units only)
Supply air static pressure controls the inverter option. A
static pressure head assembly ships separate in control
panel for field installation in the supply air duct work.
Installer is responsible for providing pneumatic tubing.
Transducer Location
Place head assembly in an area of ductwork that will
provide an average and evenly distributed airflow pattern.
Use the following guidelines to determine an appropriate
installation location.
1. Locate static head assembly approximately 2/3 to 3/4
the way down longest duct run, in an area
approximately 10 duct diameters downstream and 2
duct diameters upstream of major interferences, turns,
or changes in duct diameter.
2. When installing pneumatic tubing between head
assembly and transducer in control panel, do not
exceed 250ft for 1/4” OD tubing or 500ft for 3/8” OD
tubing.
Installing the Transducer
Use the following procedure to properly install the static
pressure transducer:
1. Mount pressure sensing head assembly in duct with
sensing tip is in middle of the duct so that it will provide
a proper pressure measurement. See Figure 24, p. 40.
2. Connect the pneumatic tubing from the sensing head to
the push-on tubing connection in the control panel. Use
a plastic static pickup tubing. Do not exceed 250 feet
for 1/4” OD tubing or 500 feet for 3/8” OD tubing.
Transducer inside control panel picks up low side or
reference pressure.
Installation - Electrical