11 GAM5-SF-1P-EN
WIRING DATA
GAM5B0B30M21SB, GAM5B0B30M21EA
Heater
Model
No.
No.
of
Circuits
240 VOLT 208 VOLT
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
kW BTUH kW BTUH
No Heater - - - 2.8* 4 15 - - 2.8* 4 15
BAYEAAC04BK1
BAYEAAC04LG1
1 3.84 13100 16.0 24 25 2.88 9800 13.8 21 25
BAYEAAC05BK1
BAYEAAC05LG1
1 4.80 16400 20.0 29 30 3.60 12300 17.3 25 25
BAYEAAC08BK1
BAYEAAC08LG1
1 7.68 26200 32.0 44 45 5.76 19700 27.7 38 40
BAYEAAC10BK1
BAYEAAC10LG1
1 9.60 32800 40.0 54 60 7.20 24600 34.6 47 50
BAYEAAC10LG3 1-3 PH 9.60 32800 23.1 32 35 7.20 24600 20.0 28 30
BAYEABC15LG3 ① 1-3 PH 14.40 49200 34.6 46 50 10.80 36900 30.0 41 45
BAYEABC15BK1 - Circuit 1②
2
9.60 32800 40 54 60 7.20 24600 34.6 47 50
BAYEABC15BK1 - Circuit 2 4.80 16400 20 25 25 3.60 12300 17.3 22 25
Note: * Motor Amps
① 208 V not approved for upflow installations
②MCA and MOP for circuit 1 contains the motor amps
WIRING DATA
GAM5B0B36M31SB, GAM5B0B36M31EA
Heater
Model
No.
No.
of
Circuits
240 VOLT 208 VOLT
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
kW BTUH kW BTUH
No Heater - - - 4.1* 5 15 - - 4.1* 5 15
BAYEAAC04BK1
BAYEAAC04LG1
1 3.84 13100 16.0 25 25 2.88 9800 13.8 22 25
BAYEAAC05BK1
BAYEAAC05LG1
1 4.80 16400 20.0 30 30 3.60 12300 17.3 27 30
BAYEAAC08BK1
BAYEAAC08LG1
1 7.68 26200 32.0 45 45 5.76 19700 27.7 40 40
BAYEAAC10BK1
BAYEAAC10LG1
1 9.60 32800 40.0 55 60 7.20 24600 34.6 48 50
BAYEAAC10LG3 1-3 PH 9.60 32800 23.1 33 35 7.20 24600 20.0 30 30
BAYEABC15LG3 1-3 PH 14.40 49200 34.6 48 50 10.80 36900 30.0 42 45
BAYEABC15BK1 - Circuit 1①
2
9.60 32800 40 55 60 7.20 24600 34.6 48 50
BAYEABC15BK1 - Circuit 2 4.80 16400 20 25 25 3.60 12300 17.3 22 25
Note: * Motor Amps
①MCA and MOP for circuit 1 contains the motor amps