EasyManuals Logo

Trane 5 Series User Manual

Trane 5 Series
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #11 background imageLoading...
Page #11 background image
11 GAM5-SF-1P-EN
WIRING DATA
GAM5B0B30M21SB, GAM5B0B30M21EA
Heater
Model
No.
No.
of
Circuits
240 VOLT 208 VOLT
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
kW BTUH kW BTUH
No Heater - - - 2.8* 4 15 - - 2.8* 4 15
BAYEAAC04BK1
BAYEAAC04LG1
1 3.84 13100 16.0 24 25 2.88 9800 13.8 21 25
BAYEAAC05BK1
BAYEAAC05LG1
1 4.80 16400 20.0 29 30 3.60 12300 17.3 25 25
BAYEAAC08BK1
BAYEAAC08LG1
1 7.68 26200 32.0 44 45 5.76 19700 27.7 38 40
BAYEAAC10BK1
BAYEAAC10LG1
1 9.60 32800 40.0 54 60 7.20 24600 34.6 47 50
BAYEAAC10LG3 1-3 PH 9.60 32800 23.1 32 35 7.20 24600 20.0 28 30
BAYEABC15LG3 1-3 PH 14.40 49200 34.6 46 50 10.80 36900 30.0 41 45
BAYEABC15BK1 - Circuit 1
2
9.60 32800 40 54 60 7.20 24600 34.6 47 50
BAYEABC15BK1 - Circuit 2 4.80 16400 20 25 25 3.60 12300 17.3 22 25
Note: * Motor Amps
208 V not approved for upflow installations
②MCA and MOP for circuit 1 contains the motor amps
WIRING DATA
GAM5B0B36M31SB, GAM5B0B36M31EA
Heater
Model
No.
No.
of
Circuits
240 VOLT 208 VOLT
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
Capacity
Heater
Amps
per
Circuit
Minimum
Circuit
Ampacity
Maximum
Overload
Protection
kW BTUH kW BTUH
No Heater - - - 4.1* 5 15 - - 4.1* 5 15
BAYEAAC04BK1
BAYEAAC04LG1
1 3.84 13100 16.0 25 25 2.88 9800 13.8 22 25
BAYEAAC05BK1
BAYEAAC05LG1
1 4.80 16400 20.0 30 30 3.60 12300 17.3 27 30
BAYEAAC08BK1
BAYEAAC08LG1
1 7.68 26200 32.0 45 45 5.76 19700 27.7 40 40
BAYEAAC10BK1
BAYEAAC10LG1
1 9.60 32800 40.0 55 60 7.20 24600 34.6 48 50
BAYEAAC10LG3 1-3 PH 9.60 32800 23.1 33 35 7.20 24600 20.0 30 30
BAYEABC15LG3 1-3 PH 14.40 49200 34.6 48 50 10.80 36900 30.0 42 45
BAYEABC15BK1 - Circuit 1
2
9.60 32800 40 55 60 7.20 24600 34.6 48 50
BAYEABC15BK1 - Circuit 2 4.80 16400 20 25 25 3.60 12300 17.3 22 25
Note: * Motor Amps
①MCA and MOP for circuit 1 contains the motor amps

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane 5 Series and is the answer not in the manual?

Trane 5 Series Specifications

General IconGeneral
RefrigerantR-410A
StagesVariable Speed
ConfigurationHorizontal or Vertical
Cooling Capacity1.5 to 5 Tons
AirflowUp to 2000 CFM
Voltage208/230V