Table 6. Wireless sensing specifications
Sensor Type Sampling Rate Change of Value Trigger/Delay Heartbeat
Temperature 30 seconds 0.2°F
15 minutes
Relative Humidity 30 seconds 1% RH
CO
2
Occupied 5 minutes
Unoccupied 15 minutes
50 ppm
Occupancy
Continuous Unoccupied to Occupied:
Transmits change of state within
30 seconds.
Occupied to Unoccupied:
5–10 minutes delay (not
adjustable).
Sends unoccupied message
after 5–10 minutes without
motion.