42
BAS-SVX40K-EN
Figure 32. Removing the sensor cover
2. Starting from any screen, press and hold the ADDR button for three (3) seconds to put the sensor
into addressing mode. The GRP icon will illuminate and the corresponding number will flash. Press
the UP or DOWN arrows to set the proper Group address number.
3. Press the NEXT button. The NET icon will illuminate and the corresponding number will flash. Press
the UP or DOWN arrows to set the proper network address number.
4. Press the NEXT button. The UC ADDRESS icon will illuminate and the corresponding numbers will
flash. Press the UP or DOWN arrows to set the proper UC address number starting with the
hundreds digit. Push NEXT to set the tens digit. Finally, push NEXT again to set the ones digit..
5. Press the NEXT button. The SENSOR icon will illuminate and the corresponding number will flash.
Press the UP or DOWN buttons to set the proper sensor number. If only one sensor is to be used,
then leave the sensor number at 1. If multiple sensors are to be used, then use the UP or DOWN
arrows to set the number of sensors (maximum of 6).