Electrical Data
24 WSHP-SVX11E-EN
GEC015 220-240/50/1 8.6 7.9 28.0 1 11.1 0.70 1/12 1 10.6 15 0.0 0.0
GEC015 220-240/50/1 13.2 7.9 28.0 1 11.1 0.70 1/6 1 16.5 20 3.0 12.5
GEC015 220-240/50/1 17.4 7.9 28.0 1 11.1 0.70 1/6 1 21.7 25 4.0 16.67
GEC015 265/60/1 7.1 6.4 30.0 1 9.0 0.70 1/6 1 8.7 15 0.0 0.0
GEC015 265/60/1 11 6.4 30.0 1 9.0 0.70 1/12 1 13.8 15 2.74 10.34
GEC015 265/60/1 14.7 6.4 30.0 1 9.0 0.70 1/12 1 18.3 20 3.7 13.96
GEC018 208/60/1 10.0 9.0 30.0 1 12.6 1.00 1/6 1 12.3 20 0.0 0.0
GEC018 208/60/1 11.8 9.0 30.0 1 12.6 1.00 1/6 1 14.8 20 2.25 10.82
GEC018 208/60/1 15.4 9.0 30.0 1 12.6 1.00 1/6 1 19.3 20 3.0 14.42
GEC018 230/60/1 9.9 9.0 30.0 1 12.6 0.90
1/6 1 12.2 20 0.0 0.0
GEC018 230/60/1 12.9 9.0 30.0 1 12.6 0.90 1/6 1 16.1 20 2.76 12.0
GEC018 230/60/1 17 9.0 30.0 1 12.6 0.90 1/6 1 21.2 25 3.7 16.09
GEC018 265/60/1 8.5 7.8 30.0 1 10.9 0.70 1/6 1 10.5 15 0.0 0.0
GEC018 265/60/1 11 7.8 30.0 1 10.9 0.70 1/6 1 13.8 15 2.74 10.34
GEC018 265/60/1 14.7 7.8 30.0 1 10.9 0.70 1/6 1 18.3 20 3.7 13.96
Table 3. Console VA
Designator Controls
Deluxe with
Reheat (75 VA)
Deluxe with
El
ectric
Heat
(75 VA)
UC400-B
(75 VA)
ZN524
(75 VA) x = ON
(a)
Controller 6.0 6.0 12.5 19.5
1K1 Compressor Contactor 5.5 5.5 5.5 5.5 X
1K2 Fan Relay 9.5 9.5 9.5 9.5
2L1 Reversing Valve 5.0 5.0 5.0 5.0 X
2L2 Reheat Valve 5.0 — — —
5B3 Damper Actuator — — — —
1K10 Electric Heat Contactor — 5.5 Optional
(b)
Optional
(b)
(b)Electric heat is optional with ZN524 and UC400-B controller. If electric heat is selected, add 5.5 VA.
X
IU3 Boilerless Control Board — 3.0 N/A N/A X
Field Supplied Solenoid 7.0 7.0 7.0 7.0 X
1K6, 1K7 Reheat Relays(2) 12.5 — Optional
(c)
Optional
(c)
(c) HGR is optional with the ZN524 and UC400-B controller. If HGR is selected, add 12.5 VA.
X
1K8 Reheat Low Speed Relay — — N/A N/A X
1U1 Thermostat-Unit Mounted 6.0 6.0 N/A N/A X
Timer Delay Relay N/A N/A N/A N/A X
Total VA 56.5 47.5 39.5 46.5 61.40
Extra VA 18.5 27.5 32.5 32.5 13.60
Note: Listed VA values are for reference only. Actual values may vary with operating conditions.
Table 2. Electrical data (0.5 to 1.5 tons) (continued)
Model Volts
Total
Unit
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No. of
Comp
Cmp
MCC
Blower
Motor
FLA
Blower
Motor
hp
Fan
Motors
Minimum
Circuit
Ampacity
Maximum
Overcurrent
Protective
Device
Electric
Heat
kW
Electric
Heat
Amps
(a) Consider unit options and concurrent loads.