EasyManuals Logo

Trane BACnet BCI-R User Manual

Trane BACnet BCI-R
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
10 BAS-SVP09B-EN
Configuring the BCI-R
Rotary Dial Address Settings for Non-Trane SC Systems
For non-Trane SC systems, the Max Master value must be greater than the unique address settings
from the rotary dials. Although 999 is possible from the dials, the maximum allowed number by
BACnet is 127.
The Max Master is not adjustable in Trane SC systems. For example, if the MAC address is 101 and
the front-end system has a Max Master value of 100, the device will not be discovered.
Many systems have a minimum BACnet Device ID value. Ensure that the Device ID is greater than
this value.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane BACnet BCI-R and is the answer not in the manual?

Trane BACnet BCI-R Specifications

General IconGeneral
BrandTrane
ModelBACnet BCI-R
CategoryRecording Equipment
LanguageEnglish

Related product manuals