BAS-SVP09B-EN 17
BACnet Data Points and Configuration Property
Definitions
The BCI-R controller allows a ReliaTel control system to communicate with BACnet systems and
devices using BACnet MS/TP. This section includes information about:
• BACnet protocol implementation conformance statement (PICS)
• Object types: descriptions and configuration (refer to Tabl e 2, p. 19)
• BACnet protocol: data link layers, device address binding, networking options, and character
sets
• Object data points and configurations
BACnet Protocol Implementation Conformance Statement (PICS)
Standardized Device Profile (Annex L)
Interoperability Building Blocks (Annex K)
Profile Description Supported Profile
BACnet Advanced Application Controller (B-AAC)
BACnet Application Specific Controller (B-ASC)
9
BACnet Building Controller (B-BC)
BACnet Operator Workstation (B-OWS)
BACnet Smart Actuator (B-SA)
BACnet Smart Sensor (B-SS)
Data Sharing Description Supported BIBB
Data Sharing-ReadProperty-A (DS-RP-A)
9
Data Sharing-ReadProperty-B (DS-RP-B)
9
Data Sharing-ReadPropertyMultiple-B (DS-RPM-B)
9
Data Sharing-WriteProperty-A (DS-WP-A)
9
Data Sharing-WriteProperty-B (DS-WP-B)
9
Data Sharing-WritePropertyMultiple-B (DS-WPM-B)
9
Alarm and Event Management Description Supported BIBB
Alarm and Event-ACKI-B (AE-ACK-B)
9
Alarm and Event-Alarm Summary-B (AE-ASUM-B)
9
Alarm and Event-Information-B (AE-INFO-B)
9
Alarm and Event-Notification Internal-B (AE-N-I-B)
9
Trending Description Supported BIBB
Trending-Automated Trend Retrieval-B (T-ATR-B)
9
Trending-viewing and Modifying Trends Internal-B (T-VMT-I-B)
9