EasyManuals Logo

Trane BACnet BCI-R User Manual

Trane BACnet BCI-R
40 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
20 BAS-SVP09B-EN
BACnet Data Points and Configuration Property Definitions
Binary
Output
Object_Identifier
•Object_Name
•Object_Type
Present_Value
•Status_Flags
•Event_State
•Out_Of_Service
•Polarity
•Priority_Array
Relinquish_Default
•Object_Name
•Description
•Out_Of_Service
•Inactive_Text
•Active_Text
Present_Value
Reliability
Change_Of_State_Count
Elapsed_Active_Time
•Minimum_On_Time
Minimum_Off_Time
Relinquish_Default
•Time_Delay
Notification_Class
Event_Enable
•Polarity
•Notify_Type
•Description
•Inactive_Text
•Active_Text
•Change_Of_State_Time
Change_Of_State_Count
Time_Of_State_Count_Reset
Elapsed_Active_Time
Time_Of_Active_Time_Reset
Minimum_On_Time
Minimum_Off_Time
•Time_Delay
Notification_Class
Feedback_Value
Event_Enable
Acked_Transitions
•Notify_Type
Event_Time_Stamps
Reliability
Yes Yes, only
use
r created
objects
Binary
Va
lue
Object_Identifier
•Object_Name
•Object_Type
Present_Value
•Status_Flags
•Event_State
•Out_Of_Service
•Polarity
•Object_Name
•Description
•Out_Of_Service
•Inactive_Text
•Active_Text
Present_Value
Reliability
Change_Of_State_Count
Elapsed_Active_Time
•Minimum_On_Time
Minimum_Off_Time
Relinquish_Default
•Time_Delay
Notification_Class
•Alarm_Value
Event_Enable
•Notify_Type
•Description
•Inactive_Text
•Active_Text
•Change_Of_State_Time
Change_Of_State_Count
Time_Of_State_Count_Reset
Elapsed_Active_Time
Time_Of_Active_Time_Reset
•Priority_Array
Relinquish_Default
Minimum_On_Time
Minimum_Off_Time
•Time_Delay
Notification_Class
•Alarm_Value
Event_Enable
Acked_Transitions
•Notify_Type
Event_Time_Stamps
Reliability
Yes Yes, only
use
r created
objects
Device Object_Identifier
•Object_Name
•Object_Type
•System_Status
•Vendor_Name
Vendor_Identifier
•Model_Name
•Firmware_Revision
Application_Software_Version
Protocol_Version
•Protocol_Revision
Protocol_Services_Supported
Protocol_Object_Types_Supported
•Object_List
Max_APDU_Length_Accepted
Segmentation_Supported
APDU_Timeout
•Number_Of_APDU_Retries
Device_Address_Binding
Database_Revision
•Object_Name
•Location
•Description
•APDU_Segment_Timeout
•APDU_Timeout
•Number_Of_APDU_Retries
•Backup_Failure_Timeout
Max_Master
Max_Info_Frames
•Location
•Description
Max_Segments_Accepted
APDU_Segment_Timeout
•Max_Master
•Max_Info_Frames
•Local_Time
Local_Date
Configuration_Files
Last_Restore_Time
Backup_Failure_Timeout
Profile_Name
None None
Event
Enro
llment
Object
Object_Identifier
•Object_Name
•Object_Type
•Event_Type
•Notify_Type
Event_Parameters
Object_Property_Reference
•Event_State
Event_Enable
•Acked_Transitions
Notification_Class
•Event_Time_Stamps
•Object_Name
•Notify_Type
Object_Property_Reference
Event_Enable
Notification_Class
•None Yes Yes, only
use
r created
objects
Table 2. Descriptions and configurations (continued)
Object
Type
Required Properties Read Properties Written
(a)
Optional Properties Read
Ability
to
Create
Ability to
Delete

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane BACnet BCI-R and is the answer not in the manual?

Trane BACnet BCI-R Specifications

General IconGeneral
BrandTrane
ModelBACnet BCI-R
CategoryRecording Equipment
LanguageEnglish

Related product manuals