EasyManua.ls Logo

Trane CGAD020 - Diagnostics CH530

Trane CGAD020
85 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CGAD-SVN02C-EN 73
Type
Reset
Phase Reversal
Current L1Loss
Current L2 Loss
Current L3 Loss
Starter Module M emory Error Type 2
Power Loss
Starter Contactor Interrupt Failure
M P: Reset Has Occurred
Low Pressure Cutout
Low Suction Refrigerant Pressure
High M otor Temp/Overload Trip Cprsr A
High M otor Temp/Overload Trip Cprsr A
BAS Failed to EstablishCommunication
BAS Communication Lost
A. The external control module of the chilled water temperature setpoint received a
control voltage or current aboveor below the specified limits. (0 to 10 VDC or 4 to 10
ma).
B. The control module presented an operational failure or there is a bad contact on the
connection cable of the modules (LLID).
A. When activated, the operational reclaiming normally is interrupted by the low
pressure control. This message indicates that the low pressure control did not detect a
low pressure of 10PSI after 30 seconds after the beginning of the reclaiming.
When the reclaiming service is activated, the low pressure control did not detect a low
pressure of 10PSI after 1minute from thebeginning of the reclaiming.
Chilled Water Flow (Entering Water Temp)
Evaporator Entering Water Temp Sensor
Evaporator Leaving Water Temp Sensor
Condenser Entering Water Temp Sensor
Condenser Leaving Water Temp Sensor
Discharge Pressure Transducer
Suction Pressure Transducer
Code Diagnostic Description of Pr oblem
E5 A phase reversal was detected on the equipment's energy supply. Local
E4 The L1current sensor detected a loss of current. Local
E4 The L2 current sensor detected a loss of current. Local
E4 The L3 current sensor detected a loss of current. Local
6B6 Detecting error in the configuration in the starter module memory of the compressors. Local
1A0 The current sensors detected a three-phase power loss during the operation. If the
current is less than 10%of the nominal current, the equipment will shut down in 2.64
seconds.
Remote
CA A current level 10%higher than the maximumcurrent of operation for the equipment was
detected on one or more phases of the three-phase power supply.
Local
D9 The controller was reset after receiving a new configuration and installation of a new
version of the control software. This message is automatically deactivated and only
visualized through the log of diagnostics.
NA
B5 or B6 The equipment's suction pressure dropped below 7 psi, causing the compressor(s) to
turn off.
Local
6B6 A suction pressure below that specified for the protection system was detected. This
diagnostic will be automatically reset when thepressure reaches adequate values.
Local
BA or BC The internal thermostat of the compressor identified a high temperature or the
protection against the compressor's overload detected a current level above the
protection level established.
Local
BB or BD The internal thermostat of the compressor identified a high temperature or the
protection against the compressor's overload detected a current level above the
protection level established.
Local
390 The controller was informed that it is linked to the Management System(BAS) and
cannot make communication with it.
Remote
398 The COM M3 communication module of the controller lost communication with the
Management System(BAS)
Remote
87 External Chilled Water Setpoint Remote
8C or 8D Circuit Pumpdown Terminated Remote
Remote
8E Temperature sensor has a defect or abad contact on the connection cable of the
sensors.
Remote
8A It was detected that the temperature of the entering water fromthe evaporator is 3.6ºC
below the evaporator's leaving water temperature, which indicates a lack of water flow
through the evaporator.
AB Temperature sensor has a defect or a bad contact on the connection cable of the
sensors.
Remote
9A Temperature sensor has a defect or a bad contact on the connection cable of the
sensors.
Remote
9B Temperature sensor has a defect or a bad contact on the connection cable of the
sensors.
Remote
6B6 Pressure transducer has a defect or a bad contact on the connection cable of the
sensors.
Remote
6B6 Pressure transducer has a defect or a bad contact on the connection cable of the
sensors.
Remote
Diagnostics
CH 530