Unit Dimensions
14 WSHP-SVX01Q-EN
Figure 3. Clearance - GEV .5 to 5 tons & EXV .5 to 6Tons
A 24 inch clearance from other mechanical and electrical
equipment (where shown) is recommended for all
configurations.This will enable panel removal from the
unit for service/maintenance.
A 1 inch minimum clearance between the filter rack and any
obstacle is required for units in a free return application to
provide proper air flow to the air-to-refrigerant coil. A 12
inch minimum clearance between the filter rack and any
obstacle should be provided to properly attached
ductwork.
The 1 inch dimension shown in the back of the unit
represents the supply duct collar for the back supply
option.This clearance is needed to clear these flanges.
36"
1"
1"
UNIT FRONT
LEFT
RETURN
TOP/BACK
SUPPLY
1"
1"
24"
UNIT FRONT
36"
RIGHT
RETURN
TOP/BACK
SUPPLY
24"
Figure 4. Clearance - GEV 6 to 10 Tons
A 24 inch clearance from other mechanical and electrical
equipment (where shown) is recommended for all
configurations.The unit may be serviced through the front
access panel or remaining open sides.
24"
FRONT RETURN
TOP SUPPLY
ACCESS PANEL FOR
SHEAVES AND BELTS
24"
36"
Figure 5. Clearance - GEV 12.5 to 25 Tons
A 24 inch clearance from other mechanical and electrical
equipment (where shown) is recommended for all
configurations.The unit may be serviced through the front
access panel.
24"
CONTROL BOX
UNIT FRONT
18"
FRONT RETURN-AIR
BACK SUPPLY-AIR
36"
18"
24"