Unit Dimensions
WSHP-SVX01Q-EN 15
Figure 6. Left return/left supply (GEH/EXH)
TOP
BACK LEFT SIDE FRONT
RIGHT SIDE
BP
N
A
C
H
H
ED
J
1"
K
1/2"
DRAIN
3/4" NPTI
BLOWER
ACCESS
PANEL
F X G
OPENING
REFRIG
AND
CONTROL
ACCESS
HI VOLT
L (W.O.)
M (W.I.)
LO VOLT
14"
Q
RS
1"
1 3/8"
6 3/4"
7"
WCI mounting location
Table 4. Dimensional data left return/left supply (GEH/EXH)
GEH Unit
(60 Hz)
GEH Unit
(50 Hz) A B C D
(a)
E F x G H J K
L
NPTI
M
NPTI N P Q R
(b)
S
006, 009 006 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
012, 015 009, 012 40 20 15 20 15 6-7/8 x 9-7/8 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
018 015 46 23 18 23 18 8-1/4 x 9-3/4 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4
024, 030 018, 024 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4
035, 042 030, 036 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
Std-048 Std-042 58 33 21 29-1/2 23-1/2 13-1/8 x 11-3/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
Hi-048,
060
Hi-042,
048, 060
58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
EXH Unit
(60 Hz)
EXH Unit
(50 Hz) A B C D
(a)
E F x G H J K
L
NPTI
M
NPTI N P Q R
(b)
S
006, 009 N/A 40 20 15 20 15 6-7/8 x 8 11-1/2 4-1/2 1-3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
012, 015 N/A 40 20 15 20 15 8-1/4 x 9-3/4 11-1/2 4-1/4 3/4 1/2 1/2 38-3/4 18-3/4 13-5/8 18-1/2 3-1/4
018, 024 N/A 46 23 18 23 18 8-1/4 x 11-3/8 13-1/2 4-3/4 1-3/8 3/4 3/4 44-3/4 21-3/4 16-5/8 18-1/2 4-1/4
030, 036 N/A 50 25 19 25 20 10-1/2 x 13-1/2 17 4 1 3/4 3/4 48-3/4 23-3/4 17-5/8 23-1/2 3-1/4
042-060 N/A 58 33 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 31-3/4 19-5/8 23-1/2 5-1/2
070 N/A 58 39 21 29-1/2 23-1/2 13-7/8 x 13-7/8 18 5-1/4 1-1/2 1 1 56-3/4 37-3/4 19-5/8 23-1/2 5-1/2
Notes:
1. When a horizontal model is ordered with the same side return and supply in a ducted application, bottom filter removal is required due to limited
access on either side of the filter.
2. Equipment containing a same-side supply/return combination requires a 3 in. clearance on one side. Access to the TXV may not be possible with this
3 in. clearance.
(a)Return air opening dimension.
(b)Filter rack dimension.