Maintenance
RT-SVX055D-EN 23
Monthly Maintenance
Before completing the following checks, turn the unit OFF
and lock the main power disconnect switch open.
WARNING
Hazardous Voltage!
Disconnect all electric power, including remote
disconnects before servicing. Follow proper lockout/
tagout procedures to ensure the power can not be
inadvertently energized. Failure to disconnect power
before servicing could result in death or serious injury.
Filters
Inspect the return air filters. Clean or replace them if
necessary. Refer to the unit Service Facts for filter
information.
Condensate Overflow Switch
During maintenance, the switch float (black ring) must be
checked to ensure free movement up and down.
Cooling Season
Check the unit’s drain pans and condensate piping to
ensure that there are no blockages.
Inspect the evaporator and
co
ndenser coils for dirt,
bent fins, etc. If the coils appear dirty, clean them
according to the instructions described in “Condenser
Coil Cleaning,” p. 23.
Manually rotate the condenser f
an(s) to
ensure free
movement and check motor bearings for wear. Verify
that all of the fan mounting hardware is tight.
Inspect the F/A-R/A damper hinges and pins to ensure
that all moving parts ar
e securely mounted. Keep the
blades clean as necessary.
NOTICE
Equipment Damage!
Never turn the motor shaft by hand or with a wrench.
Forcibly turning the motor shaft can damage the gear
train and motor beyond repair.
Verify that all damper linkages m
ove freely; lubricate
with white grease, if necessary.
Check supply fan motor bearings; repair or replace the
motor as necessary.
Check the fan shaft bearings
for wear. Replace the
bearings as necessary.
Check the supply fan belt. If the belt is frayed or worn,
replace it. Refer to “Fan Belt
Adjustment—Belt Drive
Units,” p. 22 for belt replacement and adjustments.
Verify that all wire terminal connections are tight.
R
emove any corrosion present on the exterior surfaces
of the unit an
d repaint these areas.
Generally inspect the unit for unusual conditions (e.g.,
loose access panels, l
eaking piping connections, etc.).
Make sure that all retaining screw
s are reinstalled in
the unit
access panels once these checks are complete.
With the unit running, check and record the: ambient
temper
ature; compressor suction and discharge
pressures (each circuit); superheat (each circuit);
Record this data on an “operator’s maintenance log”
like the one shown in Table 6, p. 24. If the operating
pressures indicate a refrigerant shortage, me
asure the
syst
em superheat. For guidelines, refer to
“Compressor Start-Up,” p. 20.
Note: Do N
OT release refrig
erant to the atmosphere! If
adding or removing refrigerant is required, the
service technician must comply with all federal,
state and local laws.
Heating Season
Inspect the unit’s air filters. If necessary, clean or
replace them.
Check supply fan motor bearings;
repair or replac
e the
motor as necessary.
Inspect both the main unit control panel and heat
section co
ntrol box for loose electrical components
and terminal connections, as well as damaged wire
insulation. Make any necessary repairs.
Verify that the electric heat system
operates properly.
Condenser Coil Cleaning
Regular coil maintenance, including annual cleaning,
enhances the unit’s operating efficiency by minimizing:
compressor head pressure and amperage draw;
evaporator water carryover; fan brake horsepower, due to
increase static pressure losses; airflow reduction.
At least once each year, or more often
if the unit is located
in a “d
irty” environment, clean the condenser coils using
the instructions outlined below. Be sure to follow these
instructions as closely as possible to avoid damaging the
coils.
Microchannel (MCHE) Coils
NOTICE
Coil Damage!
DO NOT use any detergents with microchannel
condenser coils. Use pressurized water or air ONLY,
with pressure no greater than 600psi. Failure to do so
could result in coil damage.
For additional information regarding the proper
m
icrocha
nnel coil cleaning procedure, refer to RT-
SVB83*-EN.
Due to the soft material and thin
walls of the MCHE coils,
the traditional field maintenance method recommended