RT-SVX51H-EN
47
• Slow Flash: Normal, Not OK to Economize
• Fast Flash - 1/4 Second On / 2 Seconds Off:
– Error Code: Communications Failure
• Pulse Flash: 1/30 Second On / 1/4 Second Off: (2
Seconds between pulse sequences)
Error Code
• 1 Flash: Actuator Fault
• 2 Flashes: CO
2
Sensor
• 3 Flashes: RA Humidity Sensor
• 4 Flashes: RA Temp Sensor
• 6 Flashes: OA Humidity Sensor
• 7 Flashes: OA Temp Sensor
• 8 Flashes: MA Temp Sensor
• 9 Flashes: On-board Setpoint Failure
TTrroouubblleesshhoooottiinngg