EasyManua.ls Logo

Trane GEH 006 - Page 81

Trane GEH 006
144 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WSHP-PRC001-EN 81
Performance Data
300-Heating (0.45 ESP)
Table P-51: GEV 300 Heating Performance
Performance data is tabulated for heating at 68 F DB entering air at ARI/ISO 13256-1 rated CFM.
For conditions other than what is tabulated, multipliers must be used to correct performance. See the fan correction factors Table for CFM
other than rated and the heating correction factors for variations in entering air temperature. Data shown in bold type is performance data
at ARI/ISO 13256-1 WLHP and GLHP water only conditions. Antifreeze correction factors may be found on page 108.
RATED ESP (in. H20): 0.45 RATED GPM: 75.0 MINIMUM CFM: 8000
RATED CFM: 10000 MAXIMUM CFM: 12000
EWT GPM Htg Cap
Mbtuh
Absorb
Mbtuh
Power
kW
LWT Feet
Head
PSID
Head
SCFM ISO Cap
Mbtuh
ISO
Power
kW
ISO COP
25
37.5 198.3 119.9 20.51 18.6 4.8 2.07
10000
192.3 18.86 2.99
50.0 203.2 132.7 20.66 19.7 7.6 3.29 197.2 19.13 3.02
62.5 207.1 136.1 20.79 20.6 10.9 4.71 201.1 19.45 3.03
75.0 210.4 139.1 20.90 21.3 14.6 6.32 204.4 19.82 3.02
87.5 213.1 141.5 20.99 21.8 18.7 8.09 207.1 20.25 3.00
GLHP
32
37.5 216.9 144.8 21.12 24.3 4.8 2.07
10000
210.8 19.47 3.17
50.0 222.2 149.5 21.30 26.0 7.6 3.29 216.2 19.78 3.20
62.5 226.8 153.6 21.46 27.1 10.9 4.71 220.8 20.12 3.22
75.0 230.7 157 21.59 27.8 14.6 6.32 224.6 20.52 3.21
87.5 233.8 159.7 21.70 28.4 18.7 8.10 227.8 20.97 3.18
45
37.5 252.4 176.1 22.36 35.6 4.8 2.07
10000
246.4 20.71 3.49
50.0 259.4 182.2 22.61 37.7 7.6 3.29 253.4 21.08 3.52
62.5 267.0 188.9 22.87 39.0 10.9 4.71 260.9 21.54 3.55
75.0 272.0 193.3 23.06 39.8 14.6 6.32 266.0 21.98 3.55
87.5 274.6 195.6 23.15 40.5 18.7 8.10 268.6 22.41 3.51
55
37.5 281.3 201.5 23.38 44.3 4.8 2.07
10000
275.3 21.73 3.71
50.0 289.7 208.9 23.68 46.6 7.6 3.29 283.7 22.16 3.75
62.5 297.0 215.3 23.94 48.1 10.9 4.71 290.9 22.60 3.77
75.0 303.1 220.7 24.15 49.1 14.6 6.32 297.0 23.08 3.77
87.5 308.1 225.1 24.33 49.9 18.7 8.09 302.1 23.60 3.75
WLHP
68
37.5 320.7 236.1 24.78 55.4 4.8 2.07
10000
314.7 23.13 3.99
50.0 331.2 245.4 25.14 58.2 7.6 3.28 325.2 23.62 4.04
62.5 340.3 253.4 25.46 59.9 10.9 4.70 334.3 24.12 4.06
75.0 348.0 260.2 25.73 61.1 14.6 6.30 342.0 24.65 4.07
87.5 354.4 265.8 25.95 61.9 18.7 8.08 348.4 25.21 4.05
75
37.5 342.9 255.7 25.55 61.3 4.8 2.06
10000
336.9 23.90 4.13
50.0 354.6 266 25.96 64.3 7.6 3.28 348.6 24.43 4.18
62.5 364.8 275 26.31 66.2 10.8 4.69 358.8 24.97 4.21
75.0 373.4 282.6 26.60 67.4 14.5 6.29 367.4 25.53 4.22
87.5 380.5 288.9 26.85 68.4 18.6 8.07 374.5 26.11 4.20
86
37.5 378.8 287.4 26.79 70.6 4.8 2.06
10000
372.8 25.14 4.35
50.0 392.4 299.4 27.26 74.0 7.6 3.27 386.4 25.73 4.40
62.5 404.2 309.8 27.66 76.0 10.8 4.68 398.2 26.32 4.43
75.0 414.2 318.6 28.00 77.5 14.5 6.28 408.2 26.92 4.44
87.5 422.5 325.9 28.29 78.5 18.6 8.04 416.5 27.55 4.43
Table P52: 300 Correction Factor for Variation in Entering Air Temperature
Cooling
Entering
Air WB F
Cooling
Capacity
Cooling
Input
Watts
Sensible vs Entering Dry Bulb
Multipliers
Heating
Entering
Air DB F
Heating
Capacity
Heating
Input
Watts
65.6 70.6 75.6 80.6 85.6
49.4 0.942 0.988 0.991 1.053 1.116 1.180 1.244 53.0 1.031 0.912
56.3 0.943 0.988 0.806 1.015 1.118 1.181 1.245 58.0 1.021 0.939
60.3 0.944 0.988 0.634 0.842 1.051 1.182 1.246 63.0 1.010 0.968
63.2 0.960 0.992 0.506 0.716 0.924 1.134 1.247 68.0 1.000 1.000
66.2 1.000 1.000 0.583 0.793 1.000 1.211 73.0 0.991 1.034
72.1 1.098 1.020 0.529 0.739 0.949 78.0 0.982 1.070
77.1 1.182 1.035 0.511 0.722 83.0 0.973 1.108
Table P53: 300 Fan Correction Factors
Entering
SCFM
Cooling
Capacity
Sensible
Capacity
Cooling
Input
Watts
Heating
Capacity
Heating
Input
Watts
8000 0.969 0.894 0.994 0.990 1.043
9000 0.986 0.948 0.997 0.995 1.021
10000 1.000 1.000 1.000 1.000 1.000
11000 1.013 1.051 1.003 1.004 0.983
12000 1.024 1.100 1.005 1.008 0.970

Related product manuals