WSHP-PRC001-EN 83
Performance Data
300-Heating (0.65 ESP)
Table P-55: GEV 300 Heating Performance
Performance data is tabulated for heating at 68 F DB entering air at ARI/ISO 13256-1 rated CFM.
For conditions other than what is tabulated, multipliers must be used to correct performance. See the fan correction factors Table for CFM
other than rated and the heating correction factors for variations in entering air temperature. Data shown in bold type is performance data
at ARI/ISO 13256-1 WLHP and GLHP water only conditions. Antifreeze correction factors may be found on page 108.
RATED ESP (in. H20): 0.65 RATED GPM: 75.0 MINIMUM CFM: 8000
RATED CFM: 10000 MAXIMUM CFM: 12000
EWT GPM Htg Cap
Mbtuh
Absorb
Mbtuh
Power
kW
LWT Feet
Head
PSID
Head
SCFM ISO Cap
Mbtuh
ISO
Power
kW
ISO COP
25
37.5 198.3 119.9 20.51 18.6 4.8 2.07
10000
189.6 18.08 3.07
50.0 203.2 132.7 20.66 19.7 7.6 3.29 194.5 18.35 3.11
62.5 207.1 136.1 20.79 20.6 10.9 4.71 198.4 18.67 3.12
75.0 210.4 139.1 20.90 21.3 14.6 6.32 201.7 19.04 3.11
87.5 213.1 141.5 20.99 21.8 18.7 8.09 204.4 19.47 3.08
GLHP
32
37.5 216.9 144.8 21.12 24.3 4.8 2.07
10000
208.2 18.68 3.27
50.0 222.2 149.5 21.30 26.0 7.6 3.29 213.5 18.99 3.30
62.5 226.8 153.6 21.46 27.1 10.9 4.71 218.1 19.34 3.31
75.0 230.7 157 21.59 27.8 14.6 6.32 222.0 19.73 3.30
87.5 233.8 159.7 21.70 28.4 18.7 8.10 225.1 20.18 3.27
45
37.5 252.4 176.1 22.36 35.6 4.8 2.07
10000
243.7 19.92 3.59
50.0 259.4 182.2 22.61 37.7 7.6 3.29 250.7 20.30 3.62
62.5 265.4 188.9 22.82 39.0 10.9 4.71 256.7 20.70 3.63
75.0 270.5 193.3 23.00 39.8 14.6 6.32 261.8 21.14 3.63
87.5 274.6 195.6 23.15 40.5 18.7 8.10 265.9 21.63 3.60
55
37.5 281.3 201.5 23.38 44.3 4.8 2.07
10000
272.6 20.95 3.81
50.0 289.7 208.9 23.68 46.6 7.6 3.29 281.0 21.37 3.85
62.5 297.0 215.3 23.94 48.1 10.9 4.71 288.3 21.82 3.87
75.0 303.1 220.7 24.15 49.1 14.6 6.32 294.4 22.29 3.87
87.5 308.1 225.1 24.33 49.9 18.7 8.09 299.4 22.81 3.85
WLHP
68
37.5 320.7 236.1 24.78 55.4 4.8 2.07
10000
312.1 22.34 4.09
50.0 331.2 245.4 25.14 58.2 7.6 3.28 322.5 22.83 4.14
62.5 340.3 253.4 25.46 59.9 10.9 4.70 331.7 23.34 4.16
75.0 348.0 260.2 25.73 61.1 14.6 6.30 339.4 23.87 4.17
87.5 354.4 265.8 25.95 61.9 18.7 8.08 345.8 24.43 4.15
75
37.5 342.9 255.7 25.55 61.3 4.8 2.06
10000
334.2 23.12 4.24
50.0 354.6 266 25.96 64.3 7.6 3.28 345.9 23.65 4.29
62.5 364.8 275 26.31 66.2 10.8 4.69 356.1 24.19 4.32
75.0 373.4 282.6 26.60 67.4 14.5 6.29 364.7 24.74 4.32
87.5 380.5 288.9 26.85 68.4 18.6 8.07 371.8 25.33 4.30
86
37.5 378.8 287.4 26.79 70.6 4.8 2.06
10000
370.2 24.36 4.45
50.0 392.4 299.4 27.26 74.0 7.6 3.27 383.7 24.95 4.51
62.5 404.2 309.8 27.66 76.0 10.8 4.68 395.6 25.54 4.54
75.0 414.2 318.6 28.00 77.5 14.5 6.28 405.5 26.14 4.55
87.5 422.5 325.9 28.29 78.5 18.6 8.04 413.8 26.76 4.53
Table P56: 300 Correction Factor for Variation in Entering Air Temperature
Cooling
Entering
Air WB F
Cooling
Capacity
Cooling
Input
Watts
Sensible vs Entering Dry Bulb
Multipliers
Heating
Entering
Air DB F
Heating
Capacity
Heating
Input
Watts
65.6 70.6 75.6 80.6 85.6
49.4 0.942 0.988 0.991 1.053 1.116 1.180 1.244 53.0 1.031 0.912
56.3 0.943 0.988 0.806 1.015 1.118 1.181 1.245 58.0 1.021 0.939
60.3 0.944 0.988 0.634 0.842 1.051 1.182 1.246 63.0 1.010 0.968
63.2 0.960 0.992 0.506 0.716 0.924 1.134 1.247 68.0 1.000 1.000
66.2 1.000 1.000 0.583 0.793 1.000 1.211 73.0 0.991 1.034
72.1 1.098 1.020 0.529 0.739 0.949 78.0 0.982 1.070
77.1 1.182 1.035 0.511 0.722 83.0 0.973 1.108
Table P57: 300 Fan Correction Factors
Entering
SCFM
Cooling
Capacity
Sensible
Capacity
Cooling
Input
Watts
Heating
Capacity
Heating
Input
Watts
8000 0.969 0.894 0.994 0.990 1.043
9000 0.986 0.948 0.997 0.995 1.021
10000 1.000 1.000 1.000 1.000 1.000
11000 1.013 1.051 1.003 1.004 0.983
12000 1.024 1.100 1.005 1.008 0.970