WSHP-SVX01AA-EN
73
Table 48. Electrical data standard static motors (0.5 to 25 tons), single speed blower motor (6 to 25 tons) (continued)
Model No. Volts
Total
Unit FLA
Comp
RLA (ea)
Comp
LRA (ea)
No. of
Comp.
Blower
Motor
FLA
Blower
Motor hp
Fan
Motor
Num
Mini-
mum
Circuit
Ampaci-
ty
Maxi-
mum
Overcur-
rent
Protec-
tive
Device
Electric
Heat kW
(a)
Electric
Heat
Amps
(a)
GEHE120
460/60/3
18.0 7.8 52.0 2 2.40
1 1/2
1 19.95 25 — —
GEHE120
208/60/3
39.1 16.0 110.0 2 7.10 2 1 43.10 50 — —
GEHE120
230/60/3
38.2 16.0 110.0 2 6.20 2 1 42.20 50 — —
GEHE120
460/60/3
18.7 7.8 52.0 2 3.10 2 1 20.65 25 — —
GEHE120
575/60/3
13.7 5.7 38.9 2 2.30 2 1 15.13 20 — —
GEHE120
208/60/3
41.4 16.0 110.0 2 9.40 3 1 45.40 60 — —
GEHE120
230/60/3
40.2 16.0 110.0 2 8.20 3 1 44.20 60 — —
GEHE120
460/60/3
19.7 7.8 52.0 2 4.10 3 1 21.65 25 — —
GEHE120
575/60/3
14.7 5.7 38.9 2 3.30 3 1 16.13 20 — —
GEHE120
208/60/3
46.0 16.0 110.0 2 14.00 5 1 50.00 60 — —
GEHE120
230/60/3
45.0 16.0 110.0 2 13.00 5 1 49.00 60 — —
GEHE120
460/60/3
22.1 7.8 52.0 2 6.50 5 1 24.05 30 — —
GEHE120
575/60/3
16.7 5.7 38.9 2 5.30 5 1 18.13 20 — —
GEHE150
208/60/3
50.4 22.4 149.0 2 5.60
1 1/2
1 56.00 70 — —
GEHE150
230/60/3
49.6 22.4 149.0 2 4.80
1 1/2
1 55.20 70 — —
GEHE150
460/60/3
23.6 10.6 75.0 2 2.40
1 1/2
1 26.25 35 — —
GEHE150
575/60/3
17.3 7.7 54.0 2 1.90
1 1/2
1 19.23 25 — —
GEHE150
208/60/3
51.9 22.4 149.0 2 7.10 2 1 57.50 70 — —
GEHE150
230/60/3
51.0 22.4 149.0 2 6.20 2 1 56.60 70 — —
GEHE150
460/60/3
24.3 10.6 75.0 2 3.10 2 1 26.96 35 — —
GEHE150
575/60/3
17.7 7.7 54.0 2 2.30 2 1 19.63 25 — —
GEHE150
208/60/3
54.2 22.4 149.0 2 9.40 3 1 59.80 80 — —
GEHE150
230/60/3
53.0 22.4 149.0 2 8.20 3 1 58.60 80 — —
GEHE150
460/60/3
25.3 10.6 75.0 2 4.10 3 1 27.95 35 — —
GEHE150
575/60/3
18.7 7.7 54.0 2 3.30 3 1 20.63 25 — —
GEHE150
208/60/3
58.8 22.4 149.0 2 14.00 5 1 64.40 80 — —
GEHE150
230/60/3
57.8 22.4 149.0 2 13.00 5 1 63.40 80 — —
EElleeccttrriiccaall DDaattaa