WSHP-SVX01AA-EN
89
Table 51. Electrical data two speed blower motor 6 to 25 tons (continued)
Model Volts
Total
Unit
FLA
Comp
RLA
(ea)
Comp
LRA
(ea)
No. of
Comp
Blower
Motor
FLA
Blower
Motor
HP
Fan
Motors
No.
Minimum
Circuit
Ampacity
Maximum
Overcur-
rent
Protection
GEVE300
460/60/3
43.8 18.6 125 2 6.6 5 1 48.45 60
GEVE300
208/60/3
118.3 48.1 245 2 22.1
7 1/2
1 130.33 175
GEVE300
230/60/3
116.2 48.1 245 2 20.0
7 1/2
1 128.23 175
GEVE300
460/60/3
47.2 18.6 125 2 10.0
7 1/2
1 51.85 70
GEVE300
208/60/3
123.8 48.1 245 2 27.6 10 1 135.83 175
GEVE300
230/60/3
121.2 48.1 245 2 25.0 10 1 133.23 175
GEVE300
460/60/3
50.2 18.6 125 2 13.0 10 1 54.85 70
GEVE300
460/60/3
57.2 18.6 125 2 20.0 15 1 62.20 80
Table 52. Electrical minimum and maximum 0.5 to 25 tons
Digit 8 Rated Voltage
Hz
pH
Min Utiliz.
Volts
Max Utiliz.
Volts
0 115 60 1 104 126
1 208 60 1 197 229
2 230 60 1 207 253
EElleeccttrriiccaall DDaattaa