PKG-SVP01B-EN
33
Programming
(On units with hydronic or electric heat)
Morning Warmup Function: ENABLED
Morning Warmup Type: FULL CAPACITY
Factory Presets: Function = Enabled
MWU Type = Full Capacity
Possible Values: Function = Enabled, Disabled
MWU Type = Full Capacity, Cycling Capacity
1. Pressing the NEXT key will display the following screen.
(On units with hydronic heat)
Supply Air Tempering Function: DISABLED
Warm Up Outside Air Used for Ventilation
Factory Presets: Function = Disabled
Possible Values: Function = Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On cooling-only units)
Unocc Mech Cooling Function: ENABLED
Factory Presets: Function = Enabled
Possible Values: Function = Enabled, Disabled
OR
(On units with hydronic, electric, or external heat)
Unocc Mech Cooling Function: ENABLED
Unocc Heating Function: ENABLED
Factory Presets: Cooling and Heating Function = Enabled
Possible Values: Cooling and Heating Function = Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
(On units with a VCM)
OA Preheater Output Control : ENABLED
Activate If Preheat Temp Below Setpoint
Factory Presets: Control = Enabled
Possible Values: Control = Enabled, Disabled
1. Pressing the NEXT key will display the following screen.
Demand Limit Definition:
Cooling: 100 %
Factory Presets: None
Possible Values: Cooling = None, 50%, or 100%
1. Pressing the NEXT key will display the following screen.
SETUP