PKG-SVP01B-EN
35
Programming
(On units with hydronic heat)
Supply Air Temp Reset Type:
Cooling: ZONE Heating: ZONE
Factory Presets: None
Possible Values: Cooling/Heating = None, Zone, OA
1. Pressing the NEXT key will display the following screen.
(On units when zone cooling reset is selected)
Supply Air Temp Zone
Reset For Cooling:
Start Temp: 72 F End Temp: 69 F
Possible Values: Cooling/Heating = Zone, OA
Start Temp Zone = 209 OA = 70
End Temp Zone = 210 OA = 71
1. Pressing the NEXT key will display the following screen.
Supply Air Temp Outside Air
Reset For Cooling:
Start Temp: 90 F End Temp: 70 F
Possible Values: Cooling/Heating = Zone, OA
Start Temp Zone = 209 OA = 70
End Temp Zone = 210 OA = 71
1. Pressing the NEXT key will display the following screen.
(On units with outside air cooling reset selected)
Supply Air Temp Zone
Reset For Cooling:
Maximum Amount of Reset Applied: 5 F
Possible Values: SAT = Zone, OA
Reset (Zone) = 72
Reset (OA) = 72
1. Pressing the NEXT key will display the following screen.
(On units with outside air cooling reset selected)
Supply Air Temp Outside Air
Reset For Cooling:
Maximum Amount of Reset Applied: 5 F
Possible Values: SAT = Zone, OA
Reset Zone = 72
Reset OA = 72
1. Pressing the NEXT key will display the following screen.
SETUP